ACM100 User’s Manual  
 
 
 
 
Page 14 
 
 
Revision 1.2 
•  Clean the unit with a soft cloth.  Do not use chemical cleaners as they may remove 
paint or markings or may corrode the ACM100 enclosure or seals. Do not use any 
cleaners containing acetone, as they will deteriorate the plastic enclosure. 
•  Ensure that the unit is mounted securely and cannot be moved relative to the mounting 
surface.  If the unit is loose, tighten the mounting screws.  
•  Check the security of the cable connected to the NMEA 2000
®
 connector, and tighten if 
necessary. 
•  Check the security of all of the current sensor connections and voltage sensor 
connections on the top of the unit and tighten if necessary. 
 
5  Troubleshooting 
If you notice unexpected operation of the Maretron ACM100, follow the troubleshooting 
procedures in this section to remedy simple problems. If these steps do not solve your 
problem, please contact Maretron Technical Support (refer to Section 7 for contact 
information). 
 
Symptom 
Troubleshooting Procedure 
No AC power data 
visible on NMEA 2000
®
 
network. 
Ensure that the ACM100 is properly connected to the NMEA 2000
®
 
network. 
 
Ensure that the current transformers and voltage sense cables are 
properly connected to the ACM100. 
 
Ensure that the ACM100 has the appropriate NMEA 2000
®
 PGNs 
enabled as described in Section 2.5.6
 
Exported power is 
increasing when it 
shouldn’t be 
 
Imported power in not 
increasing when it 
should be 
 
Currents are showing as 
negative values when 
they should be showing 
as positive values 
The current transformer(s) are installed backwards.  Either 1) 
reinstall the current transformers in the opposite direction of 2) 
configure the ACM100 to recognize the reversed installation as 
described in Sections 2.5.5.4, 2.5.5.5, and 2.5.5.6. 
 
Power readings are not 
what I expect  
Please review carefully the installation instructions in Section 0 and 
the configuration of the circuit type in Section 2.5.3