Amana PTH154G35AXXX 规格说明表单

下载
页码 8
P
roduct
 S
PecificationS
SS-DPTAC
www.amana-ptac.com
3
P
roduCT
 s
PeCifiCATions
:  PTC m
odels
 — C
ooling
/e
leCTriC
 H
eAT
230/208 V
olts
Model 
PTC
073G***XXX
PTC
093G***XXX
PTC
123G***XXX
PTC
153G***XXX
PTC
173G*
**XXX
Voltage ³
230 / 208
230 / 208
230 / 208
230 / 208
230 / 208
Capacity (BTU/h)
7,700
9,000
11,700 / 11,500
15,000 / 14,700
16400 / 16200
Amps
 
¹⁰
3.5
4.1
5.6
7.0
8.4
Watts
 
¹⁰
670/660
805/785
1135/1105
1500/1470
1740/1720
EER
11.5/11.7
11.2/11.5
10.3/10.4
10.0/10.0
9.4
Unit without Electric Heater
Min. Circuit Amps ²
,
 ⁴
,
 ¹⁰
4.2
4.9
6.8
8.5
10.2
CFM (Cool/Wet Coil)
High
290
290
290
340
340
Low
264
264
264
314
314
CFM (Dry Coil)
High
310
310
310
360
360
Low
282
282
282
332
332
Ventilated Air, CFM (Fan Only)*
65*
65*
65*
65*
65*
Dehumidification (Pints/Hr.)
1.7
2.2
3.6
4.4
4.8
Net Weight (lbs.)
98
102
102
113
113
Ship Weight (lbs.)
113
117
119
130
130
265/277 V
olts
Model 
1, 6, 8
PTC
074G***XXX
PTC
094G***XXX
PTC
124G***XXX
PTC
154G***XXX
Voltage ¹
³
265
265
265
265
Capacity (BTU/h)
7,700
9,000
12,000
14,800
Amps
 
¹⁰
3.0
3.6
4.8
6.0
Watts
 
¹⁰
670
795
1,165
1,480
EER
11.5
11.3
10.3
10.0
Unit without Electric Heater
Min. Circuit Amps ²
,
 ⁴
,
 ¹⁰
3.6
4.4
5.9
7.4
CFM (Cool/Wet Coil)
High
290
290
290
340
Low
264
264
264
314
CFM (Dry Coil)
High
310
310
310
360
Low
282
282
282
332
Ventilated Air, CFM (Fan Only)*
65*
65*
65*
65*
Dehumidification (Pints/Hr.)
1.7
2.2
3.6
4.4
Net Weight (lbs.)
98
102
102
113
Ship Weight (lbs.)
113
117
119
130
* Actual vent CFM performance will vary due to application and installation conditions.
Notes
¹  All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit PTPWHWK4 and 
disconnect switch PSHW04A.
²  Minimum Circuit Ampacity (MCA) ratings conform to the National Electric Code; however, local codes should apply. 
³  Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts; 
maximum is 292 volts. 
⁴  Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be 
cartridge-style time-delay fuses (included and factory-installed on all Amana® brand 265-volt chassis). See heater performance 
⁵  Heating capacity and efficiency based on unit operation without condensate pump; unit automatically switches to electric 
heat at approximately 24°F outdoor ambient.
⁶  Specify two-digit heater kW size to complete model number.
⁷  R-410A refrigerant used in all systems.
⁸  All units meet or exceed ASHRAE 90.1 standards.
⁹  All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
¹⁰  Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notation 
refers to compressor only.