INSTALLATION ITEMS
Before installing fireplace, make sure you have 
the items listed below.
•  external regulator (supplied by installer, for 
propane/LP units only)
•  piping (check local codes)
•  sealant (resistant to propane/LP gas)
•  equipment shutoff valve *
•  test gauge connection*
•  ground joint union
•  sediment trap
•  tee joint
•  pipe wrench
*  A CSA design-certified equipment shutoff valve 
with 1/8" NPT tap is an acceptable alternative to 
test gauge connection. Purchase the optional CSA 
design-certified equipment shutoff valve from your 
dealer. See Accessories, page 44.
Note:
 If desired, purchase a four-sided brass trim 
kit  for  built-in  installations.  See  Accessories, 
page 44.
FIREPLACE CLEARANCES
  WARNING:  Maintain  the 
minimum  clearances  shown 
in Figure 7. If you can, provide 
greater  clearances  from  floor, 
ceiling, and joining wall.
If your fireplace is to be used with an optional 
mantel, the installation instructions included with 
your mantel shows an CSA approved method of 
attaching the fireplace/mantel system to a wall. 
IMPORTANT:
  Only  use  optional  cabinet  or 
corner mantels specified in this manual. Purchase 
the optional mantel from your dealer (see Acces-
sories, page 44).
If your fireplace is to be recessed into the wall, 
see Built-In Fireplace Installation to secure your 
fireplace into the wall.
 CAUTION: If you install the 
fireplace in a home garage
•  fireplace pilot and burner must 
be  at  least  18  inches  above 
floor.
•  locate fireplace where moving 
vehicle will not hit it.
For convenience and efficiency, install fireplace
•  where there is easy access for operation, inspec-
tion, and service
•  in coldest part of room
An  optional  blower  kit  is  available  from  your 
dealer. See Accessories, page 44. If planning to use 
blower, follow instructions provided with blower 
for power source.
Minimum Clearances For Side 
Combustible Material, Side Wall, and 
Ceiling 
A.  Clearances  from  the  side  of  the  fireplace 
cabinet to any combustible material and wall 
should follow diagram in Figure 7.
 
Example: 
The face of a mantel, bookshelf, 
etc.  is  made  of  combustible  material  and 
protrudes 3 
1
/
2
" from the wall. This combus-
tible material must be 4" from the side of the 
fireplace opening (see Figure 7).
B.  Clearances from the top of the fireplace opening 
to the ceiling should not be less than 36 inches.
C.  For mantel clearances, see Figure 11, page 12.
MINIMUM CLEARANCE TO 
COMBUSTIBLE MATERIALS
 
Top 
Left and  
Bottom
 
 
Right Sides 
and Rear
 
36" 
6" 
0"
Figure 7 - Minimum Clearance for 
Combustible to Wall 
*Minimum 16 inches from Side Wall 
*
Example
INSTALLATION
Continued
BUILT-IN FIREPLACE 
INSTALLATION
Built-in  installation  of  this  fireplace  involves 
installing fireplace into a framed-in enclosure. 
This makes the front of fireplace flush with wall. 
An optional brass trim kit accessory is available 
(see Accessories, page 44). Brass trim will extend 
past sides of fireplace approximately 1/2" . This 
will cover the rough edges of the wall opening. If 
installing a built-in mantel above the fireplace, you 
must follow the clearances shown in Figure 12, 
page 12. Follow the instructions below to install 
the fireplace in this manner.