Troubleshooting
69
7.0
T
ROUBLESHOOTING
Table 14
Troubleshooting the Liebert XDP 
Symptom
Possible Cause
Check or Remedy
Pump Will Not Energize
No main power
Check L1, L2 and L3 for rated voltage.
Loose electrical connections
Tighten connections.
Overloads tripped
Allow pump to cool. Check amp draw.
Tripped circuit breaker
Check circuit breaker to pump(s).
Incorrect phase wiring
See Table 13.
Pump Will Not Start or 
Run
No chilled water
Check and verify that there is supply chilled water to the 
Liebert XDP.
Isolation valve(s) on pump suction 
and/or discharge is closed.
Open all isolation valves completely during normal operation.
Supply chilled water is too high
Check and verify that the chilled water temperature setpoint is 
at 50°F (10°C) or lower and that there is flow on the chilled 
water side.
Liebert XD cooling modules are Off
Check Liebert XD cooling modules to make sure that they are 
On prior to starting the Liebert XDP.
Low Refrigerant Temperature
 
(high dew point)
Check alarm(s) history on Liebert XDP. The Liebert XDP was 
operating below the dew point for a significant amount of time. 
Check humidity in conditioned space, lower humidity if 
necessary to allow Liebert XDP to operate at a lower 
temperature. (Disconnect must be switched to Off then back 
On to allow Liebert XDP to reset itself).
Pressure switch not making contact
Check both differential pressure settings. If not within 6 psi, ± 1 
psi (41kPa, ±7kPa; 0.41 bars, ±0.07bars) then manually 
change accordingly.
Not enough charge
Pump Will Not Start
Chilled water valve not closing 
completely.
Wait at least 10 minutes before calibrating. Access the 
Advanced Menu>Factory Settings>Calibrate Actuator. 
Contact Liebert Services for assistance, 1-800-543-2778.
Pump Noisy
Cavitation due to vapor in pump
Check for adequate charge in system, refer to the User's 
Worn motor bearings
Replace pump
Pump is rotating in reverse
See Table 13.
Liebert XDP (Pump) 
Suddenly Stops
Low refrigerant temperature
1. Check humidity of the room along with the location of 
remote sensors. Make sure that the sensors are not in a cold 
area where there is insufficient air flow for accurate, 
representative readings.
2. Chilled Water temperature is too cold.
3. Load is too light.
Loss of power
When power is restored, the Liebert XDP will automatically 
restart.
Clogged filter dryer and/or impeller
Clean out debris
Leak in system - loss of charge
Check the entire system for leaks with a refrigerant sniffer. 
Repair as necessary.
Low chilled water temperature alarm 
and loss of flow Pump X alarm
Check supply chilled water temperature.
Supply refrigerant sensor failure 
alarm
Check wiring.
Call service.
Clogged Filter Dryer 
and/or Impeller
Debris or other contaminants in 
refrigerant
Replace.
Pipe Rattle
Loose pipe connections
Check pipe connections.
Chilled Water Valve Not 
Working
Motor operates but valve won't open
Check linkage for adjustment and be sure that it is tight on the 
valve.
No 24 VAC power to motor
Check for 24 VAC between P52-1 and P52-4.
No signal from control
Check 24 VAC at P22-1 (close) or P22-3 (open).
Motor not operating
Unplug P22 from the board. Jumper P22-5 to P52-4 for 
grounding, then jumper P22-1 to P52-1 to drive close. Remove 
jumper to close and then jumper P22-3 to P52-1 to drive open. 
If motor fails to work, replace it.