Troubleshooting
70
Motor Burnout
Check control panel for welded 
contactor contacts or welded 
overload contacts
Replace defective components.
Main 24VAC Fuse Trips
Shorts or loose connections
Check the wiring connections of the 24 VAC circuit.
Faulty circuit board
Replace the circuit board.
Unstable Pump 
Operation
R-134a pump loop overcharged
While pump is running R-134a receiver level must be within 
recommended levels (see Figure 71).
R-134a pump loop undercharged
Filter dryer clogged
remedy.
Room Becomes
Too Warm
Liebert XDP is Off
Check status of the Liebert XDP at the user interface. Turn 
system On at I/O button if system is Off.
High dew point
Check temperature and relative humidity (RH) of room. Lower 
RH setpoint if necessary to lower dew point. At normal room 
temperature of 68°F (20°C), the RH should be set to 50% or 
lower.
Liebert XD cooling modules are Off
Check Liebert XD cooling modules to make sure that they are 
On before starting the Liebert XDP.
Minimum room temperature setpoint 
is too high
Check the setpoint in the User Setpoints menu (see 
Temperature/humidity sensors 
incorrectly placed
Place the sensor on the return air side of the primary air mover 
(eg., Liebert DS). Do not install the sensor near unsealed 
doors, windows or similar areas.
Reduced Chilled Water 
Flow Rate
Clogged strainer
Clean or replace strainer
Fouled heat exchanger (no strainer 
installed)
Replace heat exchanger and install 20-40 mess strainer
Increased Refrigerant 
Temperature
Clogged strainer
Clean or replace strainer
Fouled heat exchanger (no strainer 
installed)
Replace heat exchanger and install 20-40 mess strainer
Table 14
Troubleshooting the Liebert XDP (continued)
Symptom
Possible Cause
Check or Remedy