Wiring the LR5 TempGuard: 
 
The LR5 Tempguard is supplied with a green 7-contact plug to make wiring easy.  A 
plug legend is attached to the back plate of the control.  It is summarized below: 
 
Pin 1 
 
AC Line   (polarity does not matter) 
Pin 2 
 
AC Line   (polarity does not matter) 
Pin 3 
 
Door Alarm  (polarity does not matter) 
Pin 4 
 
Door Alarm  (polarity does not matter) 
Pin 5 
 
Remote alarm    (normally open contact) 
Pin 6 
 
Remote alarm    (common) 
Pin 7 
 
Remote alarm    (normally closed contact) 
 
AC Line - Power wired into AC line of the system. 
 
Door alarm - The door alarm circuit on the LR5 detects an open or closed circuit.  
An open circuit indicates that a door has been opened while a closed circuit 
indicates that all doors are closed.  The circuit should be wired in series through 
switches attached at each door. 
  
Remote Alarm  - A relay is provided on the LR5 to signal an error condition.   
Continuity exists between pins 6 & 7 in a normal condition.  An error condition 
provides continuity between pins 5 & 6.