Aprilaire Freezer PLUS Series 用户手册

下载
页码 15
 
7
 
 
If the High Alarm is being lowered and it runs into the High Temp, it will go no lower 
than the (High Temp + 2). 
 
If the Low Alarm is being raised and it runs into the Low Temp, it will go no higher 
than the (Low Temp – 2). 
 
Control Status and Error Conditions: 
 
When the control is operating normally, the temperature detected by the sensor 
assembly is displayed on the control panel.  If the temperature gets too warm and 
reaches the High Alarm setting, the display will flash alternatively between the actual 
temperature and the message Hi.  If the temperature gets too cold and reaches the 
Low Alarm setting, the display will flash alternatively between the actual temperature 
and the message Lo.  If the sensor assembly is disconnected or gets damaged the 
display will read Er. 
 
Temperature Zones & Validation: 
 
Each refrigerator or freezer will display its own characteristics in regard to the 
temperature gradient throughout the inner chamber.  The uniformity of the 
temperature throughout the inner chamber can be influenced by many factors such 
as location of the sensor, air flow patterns, mass of the sensor, location of shelves, 
location of the product stored, quantity of the product stored, mass of the product 
stored, number of doors, insulation and frequency of door openings/closings.  Some 
temperature variation in the refrigerator or freezer should be expected and is a 
normal occurrence.  The LR5 TempGuard control monitors and controls the 
temperature at the location of its sensor assembly.  At the location of the sensor the 
temperature will be accurate to within 1 degree C. 
 
Validation can be performed on the LR5 TempGuard control by testing at a known 
temperature.  Ice water has a known temperature of 0o C.  To validate the control, 
dip the sensor assembly into a bath of ice water made from distilled water.  After 
letting the temperature settle, the LR5 TempGuard will display a temperature of 0 
degrees +/- 1 degree.  This test validates the temperature accuracy of the sensor 
assembly.