Configuration, Startup, and Operation 
 
 
of Recorder with Display 
12/03 
DR4300 Circular Chart Recorder Product Manual 
133 
4.5.2.2  Changing Control Mode and Adjusting Output Manually 
Available modes 
The recorder can operate in one of two modes. 
•  Manual: When switched to manual mode, the recorder holds its output at the last value used during 
automatic operation and stops adjusting the output for changes in process variable. In manual, the 
operator uses the keypad to adjust the output by changing the value shown in the upper display.   
 
If the switch to manual is the result of an input failure sending the channel to failsafe operation, the 
output value displayed when the controller first switches to manual will be the value of the “FAILSF” 
parameter in the control set up group. This “FAILSF” value is expressed as a percentage. The output 
can be any value between 0 % and 100 %. 
•  Automatic with Local Setpoint: In automatic local mode, the recorder uses the local setpoint and 
automatically adjusts the output to maintain the setpoint at the desired value. In this mode you can 
adjust the setpoint as described in Subsection 4.5.2.3.  
Procedure for selecting manual or automatic mode 
Table 4-29 includes procedures for selecting automatic or manual mode, and for changing the output while 
in manual. 
 
Table 4-29  Procedure for Selecting Automatic or Manual Mode 
Step Operation  Press 
Action/Result 
Selecting automatic 
mode 
MAN
AUTO
RESET
 
Until “A” indicator is ON. 
The recorder regulates its output to maintain the PV at 
the desired setpoint. 
Selecting manual 
mode 
MAN
AUTO
RESET
 
Until “M” indicator is ON. 
The recorder holds its output at the last value used 
during automatic operation and stops adjusting the 
output for changes in setpoint or process variable. 
•  If you get a “KEYERR” prompt, be sure control has 
been enabled through configuration as described 
earlier in this section. 
Adjust the output in 
manual mode 
 
or 
 
Adjust the output value while in manual mode. 
Upper Display
shows the input value. 
Lower Display
shows OT and the output value  
                            in % for the selected channel. 
Return to automatic 
mode 
MAN
AUTO
RESET
 
“A” indicator appears indicating automatic mode.