FieldServer FS-RA-CLX-FIR 用户手册

下载
页码 14
SlotServer Start-Up Guide  
 
 
 
 
 
 
 
Page 9 of 14 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA   Web: www.fieldserver.com 
Tel: (408) 262 2299   Fax: (408) 262 2269   Toll Free: (888) 509 1970   email: support@fieldserver.com 
Appendix A. Useful Features 
Refer to the Configuration Manual for useful configuration features. 
The unit may be removed under power for convenient swapping of modules.  
Appendix A.1. LED Functions 
Run
Node Off
Sys Err
LonSvc
Conf Err
Com Err
Rx
Tx
Service Pin
 
Figure 3: Diagram of SlotServer showing ports and displays 
LED 
Description 
Run 
When the SlotServer is powered up, this light will start flashing after 
approximately 2 minutes. If this light does not flash, it is an indication that the 
firmware is not running, and that the SlotServer will not be operating. 
LonSvc 
This LED indicates LonWorks activity.  Refer to Figure 3. 
NodeOff  
This light indicates that a device bound to the SlotServer on the LonWorks network 
is not communicating. Use the LonWorks Network Manager to troubleshoot the 
problem. 
Conf Err 
This light indicates an error in the configuration of the card. Since this model is 
shipped pre-configured, this light should never come on unless the card 
configuration is tampered with 
Sys Err 
This light indicates that an unexpected operation state occurred. The light can be 
reset by cycling power to the card. If the error re-occurs persistently, then contact 
FieldServer Technical support for assistance with troubleshooting after setting up 
the trade port as shown in Appendix A. 
Com Err 
This light indicates that a communication error occurred. Use the LonWorks 
Network Manager to troubleshoot the problem, or refer to the SlotServer 
configuration Manual. 
RS-485  
(R1) 
These lights are related to the RS-485 serial ports provided on the SlotServer.  The 
Rx (Receive) light will flash red if the FieldServer is receiving data.  The Tx 
(Transmit) light will flash red if the FieldServer is sending data.  (Note that due to 
the nature of 2-wire RS-485 the Rx light will flash every time the Tx light flashes 
too). The frequency of the flashing is directly related to the frequency of data 
transfer. 
The LonWorks Service pin can be used for commissioning the SlotServer 
into a LonWorks network. 
LonWorks Activity can be determined using this LED as follows: 
LON LED Activity 
Explicit  Implicit – Not 
Commissioned 
Implicit – 
Commissioned 
Off 
Flashing 
Off