Operation 
SDC / DHC  
54 EN2H-0220GE51 
R0308 
4.2.3.3.3 Individualised 
operating mode for each heating circuit 
Each heating circuit can be assigned an individualised operating 
mode. 
 
► Press 
 button. 
►  Select desired heating circuit (HC, MC-1 or MC-2) by turning 
the input button 
î
►  Confirm selected circuit by pressing the input button 
î
►  Select flashing operating mode by turning the input button 
î
►  Confirm set operating mode by pressing the 
 button or the 
input button 
î
►  With short-term operating modes (ABSENT, PARTY), set 
desired target value by turning the input button 
î
 and confirm 
set value by pressing the input button 
î
Alternative: Automatic acceptance of the value after the set 
information time (see  4.1.2.7  "System information" button, pg. 26). 
 
Pos: 50 /156-Honeywell/Bedienung/Sommer_Heizgrenze @ 1\m od_1207647058244_6.doc @ 9900 
 
4.2.3.4  Summer / Heating limit 
This parameter specifies the end of heating operation depending 
on the outside temperature based on the following criteria: 
 
Quick increase in outside temperature 
If the averaged outside temperature is below the set value and 
the current outside temperature is 2 K above the set value, 
heating operation is interrupted. 
 
Slow increase in outside temperature 
Deactivation is also initiated when the averaged and current 
outside temperature exceeds the set value. 
 
Setting
C