Undoing deactivation 
Deactivation is undone when the averaged and current outside 
temperature exceeds the set value by 1 K. 
The summer deactivation function is undone: 
•  In case of an outside sensor defect 
•  In case frost protection is active 
 
During deactivation phases (standby mode, manual summer 
operation, summer deactivation) lasting longer than 24 hours all 
pumps are switched on for approx. 20 s and the mixers are 
temporarily opened during this time to protect against blocking by 
corrosion. 
In connection with a second outside sensor, the current averaged 
outside temperature is accepted for summer deactivation if the 
average value of both sensors is specified during outside sensor 
assignment. 
Active summer deactivation is represented by a beach umbrella 
symbol in the basic display. 
Only active in the AUTOMATIC operating mode. 
 
20 °C 
 
OFF, set value of system frost protection to 40 °C 
 
Pos: 51 /156-Honeywell/Bedienung/Parameter-Reset @ 1\mod_1207647099619_6.doc @ 9915 
 
4.2.3.5 Parameter 
reset 
With the reset parameter, it is possible to reset any inadvertently 
made changes in the parameter menu to the factory setting. 
 
 ATTENTION 
A reset should only be carried out if all individually entered 
values are to be replaced by the values specified at the 
factory. 
 
►  When the PARAM. RESET display flashes, press the input 
button 
î
SET flashes in the display.  
►  Press and hold the input button 
î
 for 5 s. 
 
NOTE