Honeywell SDC Benutzerhandbuch

Seite von 64
Operation 
SDC / DHC  
56 EN2H-0220GE51 
R0308 
If a reset is carried out, the RESET OK confirmation appears 
briefly. Verification is then started with a call-up of the first 
parameter in the respective menu once again. 
 
After the parameter values are reset, a return to the first 
parameter in the "System Parameter" menu occurs. 
 
Pos: 52 /156-Honeywell/Bedienung/Menue_Warmwasser @ 1\mod_1207647138228_6.doc @ 9930 
 
4.2.4 "DHW" 
menu 
This menu contains all parameters required to program the hot-
water circuit, except the hot-water switching time programs. 
 
Pos: 53 /156-Honeywell/Bedienung/Warmwassert-Nachttemperatur @ 1\mod_1207647183619_6.doc @ 9945 
 
4.2.4.1 Night-time 
hot-water 
temperature 
This parameter specifies the temperature in the hot-water 
generator between the operational-readiness times in automatic 
mode. 
 
40 °C 
 
5 °C to set normal hot-water temperature value 
 
If a hot-water thermostat (see parameter 05 = transducer for hot-
water circuit) is used to detect the hot-water temperature, this 
parameter is skipped. 
 
Pos: 54 /156-Honeywell/Bedienung/Legionellenschutz_Tag @ 1\mod_1207647218838_6.doc @ 9960 
 
4.2.4.2  Legionella protection day 
OFF 
 
OFF, MO to SU, ALL 
 
OFF 
The legionella protection function is not active. 
MO to SU 
Legionella protection is activated on the selected 
day of the week at the legionella protection time set 
in the following parameter. 
ALL 
The legionella protection function is activated daily 
at the legionella protection time set in the next 
parameter. 
 
Factory setting
Setting range
NOTE
Factory setting
Setting range
Set values