Generac 04675-3 Benutzerhandbuch

Seite von 59
  12 
2.6   ADJUSTING THE REGULATOR 
(NATURAL GAS ONLY)
Although  the  generator  has  been  factory  set  to  pro-
vide  maximum  power,  it  may  be  necessary  in  some 
areas to adjust this setting. Because natural gas has 
different  BTU  or  power  content  across  the  country 
the engine may not perform as designed.
If  experiencing  engine  problems  at  high  or  full  load 
conditions  follow  these  steps.  It  will  require  a  fre-
quency meter to perform this procedure.
1.  Turn  off  utility  power  to  the  main  distribution 
panel in the house. This can be done by switching 
the service main breaker to the off or open posi-
tion.
2.  Allow  the  generator  to  start  before  loading  the 
generator.  Confirm  the  no-load  frequency  with 
the roof open and door off is set at 63-63.5 Hz. 
Transfer load to emergency circuits.
3.  Turn on appliances, lights, pumps, etc., that are 
on  the  emergency  circuits  in  an  attempt  to  fully 
load  the  generator.  Be  cautious  not  to  overload 
the generator. Use the following chart as a guide:
4.  When 3/4 load has been achieved. Connect a fre-
quency meter to the output lugs of the generator’s 
main line circuit breaker.
5.  The fuel regulator is fitted with one (7 kW), or two 
(12 & 15 kW) adjustment screws. While watching 
the frequency meter, slowly turn the adjustment 
screw  clockwise  or  counterclockwise  one  at  a 
time until highest frequency is read on the meter. 
Only limited adjustment is available between the 
set pins. Under no circumstances should any of 
the pins be removed (Figures 2.1 and 2.2).
Figure 2.1 — Dual Fuel Regulators
410
Adjustment
Screw
(One Side
Only)
Set
Pin
V-twin
Adjustment
Screw
(Both Sides)
Set Pin
(Both Sides)
6.  When the highest frequency is reached maximum 
power has been set. Then turn both adjustment 
screws  1/4  turn  counterclockwise.  Regulator  is 
now set.
Figure 2.2 — Placement of Regulator
Adjustment Screw
7.  Turn utility power to the main distribution panel 
back on. This can be done by switching the ser-
vice  main  breaker  to  the  on  or  closed  position. 
Allow the generator to shut down.
  Do not make any unnecessary adjustments. 
Factory settings are correct for most applica-
tions. However, when making adjustments, be 
careful to avoid overspeeding the engine.
If  this  procedure  or  equipment  are  not  available, 
locate  the  nearest  Authorized  Dealer  and  they  can 
perform the adjustments.
NOTE:
A service fee may be charged for this adjustment.
2.7  ENGINE GOVERNOR ADJUSTMENT
If both AC frequency and voltage are correspondingly 
high or low, adjust the engine governor as follows:
2.7.1  7 KW UNITS
1.  Loosen the governor clamp bolt (Figure 2.3).
2.  Hold the governor lever at its wide open throttle 
position, and rotate the governor shaft clockwise 
as  far  as  it  will  go.  Then,  tighten  the  governor 
lever clamp bolt to 70 inch-pounds (8 N-m).
3.  Start the generator; let it stabilize and warm up 
at no-load.
4.  Connect  an  AC  frequency  meter  across  the  gen-
erators AC output leads.
5.  Turn  the  primary  adjust  screw  to  obtain  a  fre-
quency  reading  of  61.5  Hz.  Turn  the  secondary 
adjust  screw  to  obtain  a  frequency  reading  of 
62.5 Hz.
Section 2 — Post Installation Start-up and Adjustments
Air-cooled 7 kW, 12 kW and 15 kW Generators
 
Unit 
120 Volts 
240 Volts
 
7 kW 
50.0 amps 
25.0 amps
 
12 kW 
83.3 amps 
41.6 amps
 
15 kW 
108.3 amps 
54.1 amps