Section 2 — Post Installation Start-up and Adjustments
Air-cooled 7 kW, 12 kW and 15 kW Generators
6.  When frequency is correct at no load, check the 
AC voltage reading. If voltage is incorrect, the volt-
age regulator may require adjustment.
Figure 2.3 — Single Cylinder Engine Governor 
Adjustment
GOVERNOR
SHAFT
PRIMARY
ADJUST
SCREW
GOVERNOR
CLAMP
BOLT
SECONDARY
ADJUST SCREW
2.7.2  12 KW AND 15 KW UNITS
1.  Loosen governor clamp bolt (See Figure 2.4).
Figure 2.4 — V-twin Engine Governor 
Adjustment
Governor Clamp Bolt
Governor
Shaft
(Rotate
Clockwise)
Idle Spring
No Load Idle
Adjustment Screw
2.  Completely remove the idle spring.
3.  With governor arm at wide open throttle position, 
rotate  governor  shaft  fully  clockwise.  Tighten 
clamp bolt to 84 inch-pounds.
4.  Start unit and apply full load. Use full load speed 
adjust  screw  (Figure  2.5)  to  adjust  frequency  to 
58 Hz.
5.  Remove load, stop engine, loosen the idle adjust 
screw and reconnect the idle spring.
6.  Using  a  hand,  push  the  governor  arm  to  the 
closed throttle position. Make sure the idle spring 
does not stretch at all.
7.  Restart the unit.
8.  Slowly turn the idle adjust screw to adjust the no-
load idle frequency to 63-63.5 Hz.
9.  The governor is now set.
Figure 2.5 — V-twin Full Load Speed Adjust 
Screw
Full Load Speed Adjust Screw
2.7.3   ADDITIONAL CORROSION 
PROTECTION
Periodically spray all engine linkage parts and brack-
ets with corrosion inhibiting spray such as WD-40 or 
a comparable product.
2.8   VOLTAGE REGULATOR 
ADJUSTMENT
With  the  frequency  between  62-63.5  Hertz,  slowly 
turn the slotted potentiometer (Figure 2.6) until line 
voltage reads 244-252 volts.
NOTE:
Remove  the  access  panel  on  top  of  the  control 
panel to adjust the voltage regulator.
Figure 2.6 – Voltage Adjustment Potentiometer