HE360 HUMIDIFIER AND INSTALLATION KIT
69-2517EF—01
4
Fig. 5. Installing humidifier on duct.
11. Reinstall the humidifier pad assembly in the humidi-
fier housing.
IMPORTANT
Be sure to reconnect the water feed tube and 
ensure that the tube is not pinched or kinked.
12. Hinge the cover in place and secure with the thumb-
screw located at the bottom of the cover.
Connecting the Plumbing
1. Shut off the water.
CAUTION
Chemical Hazard. 
Can cause personal injury or equipment 
damage.
Do not use any line connected to an air 
conditioner. 
Do not use gas line.
2. First, connect 1/4-in. line to the humidifier’s sole-
noid valve, located at the bottom of the humidifier.
a. Remove the compression nut.
b. Discard the brass ring, replacing it with the plas-
tic ring.
c. Install the brass insert into the end of the tubing.
d. Insert the tubing into the solenoid valve fitting 
and support the valve while tightening the com-
pression nut.
NOTE: Do not over-tighten the compression nut. Moder-
ate tightness prevents leaking.
3. Use the saddle valve (included) to tap into the water 
supply line at the location selected.  See Fig. 8.  If 
tapping into galvanized pipe, drain line and pre-drill 
3/17-in. tap for saddle valve.
NOTE: The saddle valve is not designed to regulate 
water flow.  The valve is either open or closed.
IMPORTANT
To prevent debris from clogging the solenoid in-
line filter, be sure to install the saddle valve han-
dle pointing toward the ceiling.
Fig. 6. Installing feed tubing.
4. Use 1/4-in. (6mm) OD tubing and connect the sad-
dle valve to the inlet side of the solenoid valve on 
the humidifier (See Fig. 9).
5. Repeat step 2, a - d for saddle valve fitting.
NOTE: Cut tubing to correct length so the tubing termi-
nates at the drain.
Fig. 7. Installing the drain tubing.
Air Pressure Switch Installation
IMPORTANT
Do not install the switch in an area where tem-
perature exceeds rating of -40F to 190F (-40C to 
88C)
1. Disconnect power from the humidifier before install-
ing.
2. Mount the switch vertically with pressure connec-
tors facing down, using provided self-tapping 
screws to secure the switch to the duct.
DUCT
LEVEL
SHEET METAL
SCREWS (4)
PLASTIC
TABS (2)
DRAIN TUBING
M20204
OPENING
TO AIR DUCT
M20176
BRASS COMPRESSION NUT
PLASTIC 
COMPRESSION RING
BRASS INSERT
M20177