Honeywell HE360 Installationsanleitung

Seite von 8
HE360 HUMIDIFIER INSTALLATION KIT
69-1572
4
d. Insert the tubing into the solenoid valve fitting 
and support the valve while tightening the com-
pression nut.
NOTE:
Do not over-tighten the compression nut. Mod-
erate tightness prevents leaking.
e. Repeat steps a. through d. for solenoid valve 
fitting.
f.
Secure tubing with clamps provided.
Fig. 6. Installing feed tubing.
4.
Connect a 1/2 in. (13 mm) drain tube to the humid-
ifier drain fitting and run to the floor drain (see Fig. 
7).
a. Slide the drain clamp over the tubing.
b. Push the tubing over the drain nipple on the 
humidifier.
c. Hand-tighten the clamp around the tubing to 
secure the humidifier drain.
d. Fasten the drain tubing (can use duct tape) 
along the route to prevent movement and 
ensure downward slope for correct drainage.
NOTE:
Cut tubing to correct length so the tubing termi-
nates at the drain.
Fig. 7. Installing drain tubing.
Installing Sail Switch
Adapting Switch to Air Flow Direction
The S688A Sail Switch is provided with two 
counterbalancing springs in place as shown in Fig 8. 
These springs offset the effect of gravity for air flow 
direction.
IMPORTANT: 
Do not use the sail switch with both springs 
attached. Be sure to select air flow direction and 
remove spring(s) not required for installation.
Fig. 8. Adapting sail switch to air flow direction or 
mounting position.
Vertical 
downward
 air flow: Leave the spring in 
place that is attached to the bracket marked Down. 
Remove the spring that is attached to the bracket 
marked Up.
Vertical 
upward
 air flow: Leave the spring in place 
that is attached to the bracket marked Up. Remove 
the spring that is attached to the bracket marked 
Down.
Horizontal air flow: Remove both springs.
1.
Mount the template (provided with the sail switch) 
at the desired location.
NOTE:
Be sure the arrow (indicating air flow) points in 
the correct direction.
a. For horizontal mounting, 
level
 the long dimen-
sion shown on the template. 
b. For vertical mounting,
 plumb
 the long dimen-
sion.
2.
Cut the hole (indicated on the template) in the duct-
work.
3.
Center punch the screw holes indicated and drill 
out with a 1/8 in. (13 mm) drill.
4.
Attach the sail to the switch as shown in Fig 9.
M20176
BRASS COMPRESSION NUT
PLASTIC 
COMPRESSION RING
BRASS INSERT
M20177
UP
M3014