Start-Up
32
 GHND-SVX01C-EN
Gas Equipment Start-Up
  
 
Customer _____________________________________________
Job Name & Number _________________________
Pre-Inspection Information with Power and Gas Off
Type of Equip:
Unit Heater
Serial Number: _________________________
Model Number: _____________________________
Name Plate Voltage: ____________________
Name Plate Amperage: ______________________
Type of Gas:
Natural
LP
Tank Capacity:
_______ lb
Rating: 
_______ Btu @ ____ °F
_______ kg
________ kW @   ____ °C
 Are all panels, doors, vent caps in place?
 Has the unit suffered any external damage?
Damage ______________________________
 Does the gas piping and electric wiring appear to be installed in a professional manner?
 Has the gas and electric been inspected by the local authority having jurisdiction?
 Is the gas supply properly sized for the equipment?
 Were the installation instructions followed when the equipment was installed?
 Have all field installed controls been installed?
 Do you understand all the controls on this equipment? If not, contact your wholesaler or rep. (DO NOT START 
this equipment unless you fully understand the controls.)
Remarks: _____________________________________________________________________________________________________
_______________________________________________________________________________________________________________
_______________________________________________________________________________________________________________
GENERAL
With power and gas off.
 Make certain all packing has been removed.
 Tighten all electrical terminals and connections.
 Check all fans and blowers for free movement.
 Check all controls for proper settings.
BLOWER
With power on and gas off.
 Check voltage L1 _____ L2 _____ L3 _____
 Check rotation of main fan.
 Check motor amps L1 _____ L2 _____ L3 _____
GAS HEATING
With power and gas on.
 Inlet gas pressure. ____ in. wc or ____ kPa
 Pilot and main burner ignition.
 Manifold gas pressure. ____ in. wc or ____ kPa
 Check electronic modulation. Set at: __________
 Cycle and check all other controls not listed.
 Entering air temp. _____ °F or ____ °C
 Discharge air temp. (high fire) ____ °F. or ____ °C