Electrical Requirements
70304601
42
Electrical Requirements for Electric 
Models
NOTE: Minimum wire sizes are obtained from 
Canadian Electrical Code for 75°C Conductors and 
are intended for use as a guideline only. Electrical 
connections should be made only by a qualified 
electrical contractor in accordance with all 
applicable local and national requirements.
NOTE: Electrical specifications below are subject 
to change without notice. Always refer to product 
serial plate for most current specifications of 
product being installed.
NOTE: Connect to individual branch circuit.
NOTE: 3 Phase Only – Each tumbler must be 
connected to its own individual branch circuit 
breaker, not fuses, to avoid the possibility of “single 
phasing” and causing premature failure of the 
motor(s).
For 21 kW T30 Electric Models:
Table 11 
Serial Plate
Voltage
Terminal Block
Connections
Required
Current
(Amps)
Recommended
Breaker Rating 
(Amps)
Breaker
Poles
Recommended
Minimum
Conductor Size
[AWG (mm
2
)]
200-208V/60Hz/3ph*
L1, L2, L3,
and ground
62**
80
3
4 (21.2)
200V/50Hz/3ph*
L1, L2, L3, 
and ground
60**
80
3
4 (21.2)
230-240V/50Hz/3ph*
L1, L2, L3, 
and ground
55**
70
3
4 (21.2)
240V/60Hz/3ph*
L1, L2, L3,
and ground
54**
70
3
4 (21.2)
380V/50 or 60Hz/3ph*
L1, L2, L3, 
and ground
33**
45
3
8 (8.37)
400-415V/50Hz/3ph*
L1, L2, L3, 
and ground
31**
40
3
8 (8.37)
460-480V/60Hz/3ph*
L1, L2, L3, 
and ground
27**
35
3
8 (8.37)
These serial plate voltages are only options available on the T30 electric models. Current (Amp) is for one pocket only. 
**  Per heater on T30 electric models, each has two heaters.