Whirlpool W10392127B-SP User Manual

Page of 36
17
TROUBLESHOOTING
DRYER OPERATION
Dryer will not run
 
Has a household fuse blown, or has a circuit breaker 
tripped? 
There may be two household fuses or circuit breakers  
for the dryer. Check that both fuses are intact and tight,  
or that both circuit breakers have not tripped. Replace  
the fuse or reset the circuit breaker. If the problem  
continues, call an electrician.
 
Is the correct power supply available? 
Electric dryers require a 240-volt power supply. Check  
with a qualified electrician.
 
Was a regular fuse used? 
Use a time-delay fuse.
No heat
 
Has a household fuse blown, or has a circuit breaker 
tripped? 
The drum may be turning, but you may not have heat. 
Elelctric dryers use two household fuses or circuit breakers.
Replace the fuse or reset the circuit breaker. If the problem  
continues, call an electrician.
 
Is “Check Vent” illuminated on the Airflow screen? 
This indicator will show the status of airflow through the 
dryer vent. The Detecting light comes on during the sensing 
phase at the beginning of a cycle. The Check Vent light will 
come on if a blocked vent or low airflow issue is detected. 
 
  Try  the  following:   
Clean lint screen. 
 
Check to see if the vent run from the dryer to the wall is free 
of lint and debris. 
 
Confirm the exterior vent exhaust hood is free of lint and 
debris. 
 
Confirm your vent system falls within the recommended run 
length and number of elbows for the type of vent you are 
using. Refer to “Plan Vent System” for details. 
 
Select a Timed Dry heated cycle, and restart the dryer.
For more information on maintaining good airflow, see 
“Check Your Vent System for Good Airflow” in the “Use and 
Care Guide”. If the message persists, have your entire home 
venting run cleaned.
Dryer displaying code message
 
“PF” (power failure), check the following: 
Was the drying cycle interrupted by a power failure? 
Press and hold START/PAUSE to restart the dryer. 
 
   Try  the  following:   
Check to see if a household fuse has blown or circuit breaker 
has tripped. Electric dryers use two household fuses or 
breakers. Replace the fuse or reset the circuit breaker. 
 
Confirm the power cord is properly installed. 
 
Select a Timed Dry heated cycle, and restart the dryer. 
 
If the message persists, consult a qualified electrician.
 
“F” Variable (F1E1, F2E2, F3E1, F3E2, F7E1, F3E6, F3E7) 
service codes: 
Call for service.
DRYER RESULTS
Clothes are not drying satisfactorily, drying times are 
too long, or load is too hot
 
Is the lint screen clogged with lint? 
Lint screen shold be cleaned before each load.
 
Is the exhaust vent or outside exhaust hood clogged with 
lint, restricting air movement? 
Run the dryer for 5-10 minutes. Hold your hand under 
the outside exhaust hood to check air movement. If you 
do not feel air movement, clean exhaust system of lint or 
replace exhaust vent with heavy metal or flexible vent. See 
“Installation Instructions.”
 
Are fabric softener sheets blocking the grille? 
Use only one fabric softener sheet, and use it only once.
 
Is the exhaust vent the correct length? 
Check that the exhaust vent is not too long or has too 
many turns. Long venting will increase drying times. See 
“Installation Instructions.”
 
Is the exhaust vent diameter the correct size? 
Use 4" (102 mm) diameter vent material.
 
Is the dryer located in a room with temperature below 
45°F (7°C)? 
Proper operation of dryer cycles requires temperatures 
above 45°F (7°C).
 
Is the dryer located in a closet? 
Closet doors must have ventilation openings at the top and 
bottom of the door. The front of the dryer requires a minimum 
of 1" (25 mm) of airspace, and, for most installations, the 
rear of the dryer requires 5" (127 mm). See “Installation 
Instructions.”