Thermo Products CMC1-75DV3N User Manual

Page of 65
All installations and services must be performed by qualified service personnel. 
 
CMC1-75DV3 
ALTERATIONS REQ’D FOR A/C @ DESIGN EXTERNAL STATIC PRESSURE 
COOLING UNIT 
HTG Speed 
Recommended CLG Speed 
24,000 
MED-LOW 
MED-LOW 
30,000 
MED-LOW 
MED-HIGH 
36,000 
MED-LOW 
HIGH 
 
 
Speed Tap \ 
Static 
Pressure 
Furnace Airflow (CFM) vs. External Static pressure (in. WC.) 
0.1 
0.2 
0.3 
0.4 
0.5 
0.6 
0.7 
Low 
970 
935 
898 
846 
802 
765 
710 
ML 
1043 
998 
968 
928 
880 
830 
785 
MED 
1148 
1113 
1080 
1051 
1007 
968 
929 
MH 
1212 
1177 
1142 
1119 
1083 
1047 
1023 
High 
1300 
1272 
1229 
1211 
1177 
1144 
1117 
 
 
 
 
 
 
 
 
 
 
 
 
 
Speed Tap \ 
Static 
Pressure 
Blower Motor Current Draw (Amps) vs. External Static pressure (in. WC.) 
0.1 
0.2 
0.3 
0.4 
0.5 
0.6 
0.7 
Low 
2.4 
2.5 
2.5 
2.6 
2.6 
2.7 
2.7 
ML 
2.8 
2.9 
3.0 
3.0 
3.1 
3.1 
3.2 
MED 
3.6 
3.7 
3.7 
3.8 
3.8 
3.9 
3.9 
MH 
4.2 
4.2 
4.3 
4.3 
4.4 
4.5 
4.5 
High 
4.8 
4.9 
5.0 
5.0 
5.1 
5.2 
5.2 
 
 
Speed Tap \ 
Static 
Pressure 
Blower Motor Watts vs. External Static pressure (in. WC.) 
0.1 
0.2 
0.3 
0.4 
0.5 
0.6 
0.7 
Low 
187 
190 
195 
200 
204 
206 
211 
ML 
225 
229 
233 
238 
244 
248 
252 
MED 
290 
295 
299 
303 
310 
315 
320 
MH 
341 
347 
353 
356 
364 
369 
371 
High 
408 
414 
423 
428 
435 
441 
445 
 
 
 
 
 
 
 
 
 
Speed Tap \ 
Static 
Pressure 
Temperature Rise vs. External Static Pressure (in. WC.) 
0.1 
0.2 
0.3 
0.4 
0.5 
0.6 
0.7 
Low 
75 
78 
81 
86 
91 
96 
103 
ML 
70 
73 
76 
79 
83 
88 
93 
MED 
64 
66 
68 
70 
73 
76 
79 
MH 
60 
62 
64 
65 
67 
70 
71 
High 
56 
57 
59 
60 
62 
64 
65 
 
Recommended operation range 
 