Ultra-Aire 90H Installer’s & Owner’s Manual
11
Ultra-Aire 90H Installer’s & Owner’s Manual
FOR HVAC INSTALLER ONLY
WARNING:
 
TO AVOID TRANSFORMER DAMAGE 
ONLY CONNECT WHITE WIRE TO CONTROL IF DAMPER IS USED.
The white wire controls the optional motorized damper 
that can be installed into a fresh air duct. This provides 
the ability to control when fresh air is introduced into the 
building by using the ventilation timer function labeled 
“DMP” on the control (See Section 3.7). If the motorized 
damper is not used, 
DO NOT CONNECT THE WHITE WIRE 
TO THE CONTROL OR DAMAGE TO THE TRANSFORMER 
MAY RESULT.
 Simply leave the (DMP) terminal unused if 
the damper is not used, and cap off the white lead fro mthe 
Ultra-Aire base unit.
5.2C Auxiliary relay operation
At times it may be desirable to coordinate fan operation 
of the central heating/cooling system with dehumidifier 
operation. The DEH 3000 features a relay that provides 
this ability. The relay terminals labeled NC, COM and 
NO operate according to the following chart:
Dehumidification  
 
Operation 
COM/NO 
COM/NC 
 
ON 
CLOSED 
OPEN
 
OFF 
OPEN 
CLOSED 
Common uses (assuming standard thermostat wiring color 
schemes as noted):
Disengage A/C during dehumidification
Redirect the yellow thermostat wire to the NC 
terminal. Wire the yellow wire from the A/C to the 
COM (B) terminal.
Engage A/C during dehumidification
Connect a wire from the “R” terminal on the the 
thermostat to the “com” terminal on the DEH 3000. 
Connect a wire from the “NO” terminal on the DEH 
3000 to the “Y1” terminal on the thermostat.
5.2D Dehumidifier lockout/activation AC sensor
The control has the ability to activate the dehumidifier or 
deactivate the dehumidifier when the air conditioner is 
running.
Standard wire colors for thermostats are as follows:
Description 
Color 
Terminal code
24VAC Return 
Red 
R
Call for Heat 
White 
W or W1
Force Fan On 
Green 
G
Compressor 
Call for Cooling 
Yellow 
Y or Y1
UA Base Unit
Yello
w
Red
Blue
Gr
een
White
DAMPER
24 
VAC
DMP
COMP
FAN
DEH 3000 Wiring Diagram
optional