Ultra-Aire 90H Installer’s & Owner’s Manual
11
Ultra-Aire 90H Installer’s & Owner’s Manual
FOR HVAC INSTALLER ONLY
5.  DEH 3000 Digital Control  
Installation Instructions
5.1 Specifications
Part # (P/N) 
4026570 
Model: 
DEH 3000 Digital Control
Electrical: 
24 VAC
Humidity Range: 
10 – 95% RH
Humidity Accuracy: 
+/- 5%
Output: 
3 Amps 24 VAC 
Relay Capacity 
5 Amps 
Temp Range/Accuracy 
2% 
Size 
4.95" wide x 4.19" high
FOR HVAC INSTALLER ONLY:
5.2 Installation
This control panel must be installed in the conditioned space 
and in accordance with all applicable codes and standards. 
Follow the instructions below when installing and setting this 
control.
5.2A Install Instructions
1.   Separate the front panel from the back panel by 
depressing the middle sections of the top and bottom of 
the front panel.
2.   Line the back panel up against the wall or flat surface 
onto which it is to be mounted and drill in the appropriate 
mounting holes.
3.   Insert the screws and tighten down so they extend 
approximately 1/8” from the back plate.
4.  Align the back panel so that the control is level.
5.  Tighten the screws to lock into position.
6.   Make the electrical connections to the terminals on the 
back panel as shown in the wiring diagram.
7.   Reassemble the front to the back panel. Connect at the top 
first, then at the bottom.
8.  Test connections (see Section 2.6)
5.2B Wiring
WARNING: 
DO NOT ALLOW THE YELLOW LEAD 
FROM THE ULTRA-AIRE TO CONTACT THE RED OR WHITE LEADS 
FROM THE ULTRA-AIRE OR DAMAGE TO THE TRANSFORMER 
WILL RESULT
WARNING: 
UNPLUG ULTRA-AIRE BASE UNIT 
BEFORE WIRING CONTROL.
The installer must supply the wiring between the Ultra-Aire 
and the control panel. Be sure to safely route the control wires 
to prevent damage during installation. Be careful not to cross 
the wires when connecting the Ultra-Aire and the remote 
control panel or damage to the transformer may result.
The remote control of the Ultra-Aire is powered by a low 
voltage circuit (24 VAC) and must 
NEVER contact or be 
connected to a high voltage circuit. Some of the control wires 
leaving the Ultra-Aire may not be used with certain control 
panels and should be left safely disconnected with wire nuts 
taped onto the stripped ends. Be sure to consult the electrical 
schematic in this manual or on the front panel of the Ultra-
Aire before making the control connections.
Control Part No. 4026570