If the foundation is recessed, 
use  recess  brackets  (not 
supplied) for securing lower 
portion  of  the  snorkel. 
Fasten  brackets 
to wall first, then 
secure to snorkel 
with  self  drilling 
#8  x  1/  sheet 
metal  screws.  It 
will be necessary 
to  extend  vent 
pipes  out  as  far 
as  the  protrud-
ing  wall  face. 
Figure 28
FP1966
snorkel
Figure 28 - 
Snorkel Installation, Recessed Foundation
Foundation
Recess 
Watertight Seal 
Around Pipe 
Sheet Metal 
Screws 
Snorkel
Wall Screws
FP1966
W
ARNING
  Do not back fill around snorkel.
  A  clearance  of  at  least  4"  must  be 
maintained between the snorkel and 
the soil.
VeRtICAl tHRouGH-tHe-RooF APPlICA-
tIoNS 
Install restrictor disc as shown in Figure 30 for vertically 
vented applications. 
Up  to  three  (3)  restrictor  discs  may  be  needed  for  40' 
installation. 
The two () restrictor discs suppled will work for most instal-
lations. If a third disc is needed order Part No. 56D307. 
You  may  use  a  reducer  to  4"  x  6B\,"  in  vertically  vented 
applications. 
W
ARNING
A restrictor disc must be installed on any 
vertical  termination  that  is  higher  than 
12'. 
Simpson Duravent 58DVA-VC/1280 Vertical 
Cap cannot be used with this fireplace.
FP2467
HDV restrictor
Restrictor Disc
Stove Collar
FP467
Figure 29 -
Install Restrictor Disc into Stove Collar
This Gas Fireplace has been approved for,
   Vertical installations up to 40' (1 m) in height. Up to a 
10' (3 m) horizontal vent run can be installed within the 
vent system using a maximum of two 90° elbows. See 
Figure 30
•   Up to two 45° elbows may be used within the horizontal 
run. For each 45° elbow used on the horizontal plane, 
the maximum horizontal length must be reduced by 18" 
(450 mm). 
Example: Maximum horizontal length 
  
No elbows  
=  10’ (3 m)
  1 x 45° elbows  
=  8.5’ (.6 m)
   x 45° elbows  
=  7’ (.1 m)
   A minimum of an 8' (.5 m) vertical rise is required.
   Two sets of 45°elbows offsets may be used within the 
vertical sections. From 0 to a maximum of 8' (.5 m) of 
vent pipe can be used between elbows. Figure 31
   Determine the roof pitch and use the appropriate starter 
kit for offset installation. 
FP1183
max height
10' Maximum
40' 
Maximum 
Height
8'
Minimum 
Height
Support 
Straps 
Every 5' 
Vertical 
Support Straps Every 3'
10' Maximum
40' 
Maximum 
Height
8'
Minimum 
Height
Support Straps Every 3'
FP1183
Figure 30  - 
Support Straps for Horizontal Runs