Monessen Hearth LX36DV User Manual

Page of 48
51D0528
17
LX Series Direct Vent Gas Fireplace
VeNtING INStALLAtIoN
ReAR WALL VeNt INStALLAtIoN 
When installed as a rear vent unit this appliance may be 
vented directly to a termination located on the rear outside 
termination behind the appliance
  45° elbows may only be attached to rear when used to 
direct the flue skyward (to achieve additional rise). Do 
not attach 45° elbows to rear of appliance in which the 
flue turns either left or right and terminates horizontal. 
   The  maximum  horizontal  distance  between  the  rear 
of  the  appliance  and  the  outside  face  of  the  outside 
termination is 20" (508 m). Figure 15
DVR584-600
Rear vent no elbows
2/99   djt
Figure 14 - 
Rear Vent Application, 
Maximum Horizontal Distance 
20"(508 mm)
Maximum
DVR584
1.  Locate and cut the vent opening in the wall. For com-
bustible walls first frame in opening. Figure 15 
  combustible Walls: Cut a 11Z\x"H x 9Z\x" W (292 x 24 
mm) hole through the exterior wall and frame as shown. 
Figure 15
  Noncombustible Walls: Hole opening should be 7Z\x" 
(190 mm) in diameter.
VO584-100
Vent Opening
2/99   djt
9Z\x"
(241 mm)
11Z\x"
(292 mm)
Vent opening for combustible Walls
Fireplace Hearth
Framing Detail
Vent opening for Noncombustible Wall
7Z\x"
(190 mm)
Fireplace Hearth
VO584-100
Figure 15 -
Locate Vent Opening on Wall
FP1953
rigid pipe
Figure 16 - 
Rigid Vent Pipe Connections
Note: horizontal runs of 
vent  must  be  supported 
every 3' (914 mm). use wall 
straps for this purpose. 
Female 
Locking Lugs
Male Slots
FP1953
2.  Rigid  vent  pipes  and  fittings  have  special  twist-lock 
connections. Assemble the desired combination of pipe 
and elbows to the appliance adaptor with pipe seams 
oriented towards the wall or floor.
  Twist-lock  Procedure:  The  female  ends  of  the  pipes 
and  fittings  have  three  locking  lugs  (indentations). 
These  lugs  will  slide  straight  into  matching  slots  on 
the male end of adjacent pipes and fittings. Push the 
pipe sections together and twist one section clockwise 
approximately  one-quarter  turn  until  the  sections  are 
fully locked. Figure 16
3.  Attach vent pipe assembly to the fireplace. Set fireplace 
in  front  of  its  permanent  location  to  insure  minimum 
clearances. Mark the wall for a 11Z\x"H x 9Z\x"W (292 x 24 
mm) rectangle hole (for noncombustible material such 
as masonry block or concrete, a 7Z\x" [190 mm] diameter 
hole is acceptable). Figure 15. The center of the hole 
should line up with the center line of the horizontal rigid 
vent pipe end. Be sure to allow for minimum rise.  Cut 
a 11Z\x" x 9Z\x" (292 X 241 mm) rectangle hole through 
combustible exterior wall (7Z\x" [190 mm] diameter hole 
if  noncombustible).  Frame  as  necessary. Allow  1/4" 
minimum rise per foot. Figure 15
4.  Apply  a  bead  of  non-hardening  mastic  around  the 
outside edge of vent cap. Position the vent cap in the 
center of  hole on the exterior wall with the word “UP” 
on the vent cap facing up. Insure proper clearance of 
1" to combustibles is maintained. Attach the vent cap 
with four wood screws supplied. Figure 17
Note: Replace the wood screws with appropriate fasteners 
for stucco, brick, concrete, or other types of siding. 
W
ARNING
Do  not  recess  vent  termination  into  any 
wall. this will cause a fire hazard.