Monessen Hearth LX36DV User Manual

Page of 48
51D0528
19
LX Series Direct Vent Gas Fireplace
VeNtING INStALLAtIoN
FP1176
max 90 bends
Figure 20 - 
Maximum Three (3) 90° Elbows 
Per Installation
3 x 90°
Elbows
3 x 90°
Elbows
FP1176
Max 20"
Max 20"
36"
(914 mm) 
Max.
36"
(914 mm) 
Max.
FP1177
max horizontal run
Figure 21 - 
Maximum Horizontal Run with No Rise
FP1177
  example: According to the vent graph (Page 16) the 
maximum horizontal vent length in a system with a 7.5' 
vertical rise is 20’ (6 m). If a 90° elbow is required in the 
horizontal vent it must be reduced to 17' (5.2 m). 
In  Figures  22  and  23,  Dimension A  plus  B  must  not  be 
greater than 17' (5.2 m).
   The maximum number of 45° elbows permitted per side 
wall installation is two (2). These elbows can be installed 
in either the vertical or horizontal run. 
   For each 45° elbow installed in the horizontal run, the 
length of the horizontal run MUST be reduced by 18" 
(457 mm). This does not apply if the 45° elbows are 
installed on the vertical part of the vent system.
   The maximum number of elbow degrees in a system is 
270°. Figure 24
A: 10’
B: 7’
7’6”
FP1959
max run w/elbows
Figure 22 - 
Maximum Vent Run with Elbows
Horizontal 90° Elbow = 3' Reduction
FP1959
A + B = 17' Maximum
90°
A
B
7’6”
(2.3 m)
FP2717
horiz run reduct
Figure 23 - 
Horizontal Run Reduction
FP2717
example: 
Elbow 1   =   90°
 
Elbow 2   =   45°
 
Elbow 3   =   45°
 
Elbow 4   =   90°
Total Angular Variation   =   270°
Figure 24 - 
Maximum Elbow Usage 
1
2
3
4
1
2
3
4
1 + 2 + 3 + 4 = 270°