Monessen Hearth LX32DV User Manual

Page of 48
51D0528
13
LX Series Direct Vent Gas Fireplace
VeNtING INStALLAtIoN
this fireplace must be vented to the outside. the venting system must 
NeVeR be attached to a chimney serving a separate solid fuel burning 
appliance. each gas appliance must use a separate vent system. Do not 
use common vent systems.
W
ARNING
coMBuStIBLe cLeARANceS FoR VeNt pIpe
W
ARNING
horizontal sections of this vent system require a minimum of 3" clearances 
to combustibles at the top of the flue and 1" clearance at the sides and 
bottom until the flue penetrates the outside wall. 
A minimum 1" clearance 
all around the flue is acceptable at this point of penetration.
Vertical sections of this vent system require a minimum of 1" clearance to 
combustibles on all sides of the pipe.  
1"
*3"
**1"
**1"
35(6 ”
(911 mm)
FP2713
vent clearance
Figure 10 - 
Combustible Clearances for Vent Pipe
* A  minimum  of  3"  clearance  to  the  top  is 
required along horizontal length until flue pipe 
penetrates outside wall. 
** A  minimum  1"  clearance  to  combustibles 
permitted all around flue at outside wall
FP2713