VeNtING INStALLAtIoN
X
VENT TERMINATION  
AIR SUPPLY INLET 
AREA WHERE TERMINAL IS NOT PERMITTED 
 
Fixed
Closed
Operable
Operable
Fixed
Closed
CFM145a 
DV Termin Location 
5/01/01 Rev. 12/05/01  
sta 
INSIDE 
CORNER DETAIL 
CFM145a 
GeNeRAL VeNtING INFoRMAtIoN - teRMINAtIoN LocAtIoN
  A =  Clearance above grade, veranda, porch,  
12” (30 cm) 
12” (30 cm) 
  deck, or balcony
  B =  Clearance to window or door that may be  
6” (15 cm) for appliances  
6” (15 cm) for appliances
   
opened 
< 10,000BTU/h (3kW), 12” (30 cm)  
< 10,000 BTU/h (3kW), 9” 
 
   
 
for appliances > 10,000 Btuh (3kW) and 
(23 cm) for appliances > 10,000 
   
 
< 100,000 BTU/h (30kW), 36” (91 cm) 
Btuh (3kW) and < 50,000 BTU/h 
   
 
for appliances > 100,000 BTU/h (30kW) 
(15kW), 12” (30 cm) for 
   
 
 
appliances > 50,000 BTU/h(15kW)
  C =  Clearance to permanently closed window 
12” (305 mm) recommended to 
12” (305 mm) recommended to  
   
 
prevent window condensation 
prevent window condensation
  D = Vertical clearance to ventilated soffit located   
 
 
 
 
 
  above the terminal within a horizontal  
18” (458 mm) 
18” (458 mm) 
 
 
  distance of 2’ (610mm) from the center 
 
 
 
 
 
 
  line of the terminal
  E =  Clearance to unventilated soffit 
12” (305 mm) 
12” (305 mm)
  F =  Clearance to outside corner  
see next page 
see next page
  G = Clearance to inside corner (see next page) 
see next page 
see next page
  H =  Clearance to each inside of center line 
3’ (91 cm) within a height of 15’ (5 m)  
3’ (91 cm) within a height of 15’ 
   
extended above meter/regulator assembly 
above the meter/regulator assembly 
(5 m) above the meter/regulator 
   
 
 
assy
  I =  Clearance to service regulator vent outlet 
3’ (91 cm) 
3’ (91 cm)
  J =  Clearance to nonmechanical air supply inlet  6” (15 cm) for appliances < 10,000 
6” (15 cm) for appliances
   
to building or the combustion air inlet to any  BTU/h (3kW), 12” (30 cm) for 
< 10,000 BTU/h (3kW), 9”
   
other appliances 
appliances > 10,000 BTU/h (3kW) and   
(23 cm) for appliances > 10,000
   
 
< 100,000 Btuh (30kW), 36” (91 cm) 
BTU/h (3kW) and < 50,000 BTU/h
   
 
for appliances > 100,000 BTU/h (30kW) 
(15kW), 12” (30 cm) for  
   
 
 
appliances > 50,000 BTU/h(15kW)
  K =  Clearance to a mechanical air supply inlet 
6’ (1.83 m) 
3’ (91 cm) above if within 10'   
    
 
 
(3 m) horizontally
  L =  Clearance  above paved sidewalk or paved  7’ (2.13 m)† 
 
7’ (2.13 m)†
   
driveway located on public property
  M = Clearance under veranda, porch, deck or 
12” (30 cm) 
 
12” (30cm)
   
balcony 
 
 
 
1 In accordance with the current CSA-B149 Installation Codes
2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel 
Gas Codes
† A vent shall not terminate directly above a sidewalk or paved 
driveway which is located between two single family  
 
dwellings and serves both dwellings
 only permitted if veranda, porch, deck or balcony is fully open on a 
minimum 2 sides beneath the floor:
 
 
canadian Installations
1
 
uS Installations
2
NOTE: 1. Local codes or regulations may require different    
 
  clearances.
 
2. The special venting system used on Direct Vent Fireplaces  
 
  are certified as part of the appliance, with clearances  
 
  tested and approved by the listing agency.
 
3. MHSC assumes no responsibility for the improper   
 
  performance of the appliance when the venting system  
 
  does not meet these requirements.
Figure 11 - 
Horizontal Vent Termina-
tion Locations