Monessen Hearth 624DV(ST User Manual

Page of 52
16
42D0200
Designer Series Gas Fireplaces
vENTING INSTaLLaTIoN 
TERMINaTIoN CLEaRaNCES FoR BuILdINGS wITh CoMBuSTIBLE  
aNd NoNCoMBuSTIBLE ExTERIoRS 
Figure 14 - 
Allowable Venting Chart 
how To uSE ThE vENT GRaPh
The Vent Graph should be read in conjunction with the following 
vent installation instructions to determine the relationship between 
the vertical and horizontal dimensions of the vent system.
1.  Determine the height of the center of the horizontal vent pipe exit-
ing through the outer wall. Using this dimension on the Sidewall 
Vent Graph below, locate the point intersecting with the slanted 
graph line.
2.  From the point of this intersection, draw a vertical line to the 
bottom of the graph.
3.  Select  the  indicated  dimension,  and  position  the  fireplace  in 
accordance with same.
  Example: If the vertical dimension from the floor of the fireplace 
is 11' (3.4 m) the horizontal run to the face of the outer wall must 
not exceed 14' (4.3 m).
  Example: If the vertical dimension from the floor of the unit is 
7’ (2.14m), the horizontal run to the face of the outer wall must 
not exceed 8Z\x' (2.6 m).
Sidewall Vent Graph showing the relationship between vertical and 
horizontal dimensions for a Direct Vent flue system.
Figure 15 - 
Rear Wall Venting Graph
Horizontal Dimension From the Outside Face of the 
Wall to the Center of the Fireplace Vent Flange
V
ertical Dimension From the Floor of Unit to the Center of the 
Horizontal V
ent Pipe
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
2  4  6  8 10 12 14 16 18 20
eg: A
Dimensions in 
Feet
20"
FP2248
sidewall vent graph
V
G
G=6" (152mm)
F
F=6" (152mm)
V
V
G
G = Combustible 24"(610mm)
 
Noncombustible 18"(457mm)
Combustible & 
Noncombustible
H = 24" (610mm)
J =  20" (508mm)
V
H
J
C = Maximum depth of 48" (1219mm)
    for alcove location
D = Minimum width for back wall of
    alcove location
    Combustible - 38" (965mm)
    Noncombustible - 24" (610mm)
E = Clearance from corner in alcove 
    location
    Combustible - 6" (152mm)
    Noncombustible - 2" (51mm)
E
V
D
C
C
Inside Corner 
Alcove Location
Outside Corner 
Balcony with No Side Wall
Balcony with Perpendicular
Side Wall
FP1951
termination clearances