Monessen Hearth WDV500 User Manual

Page of 48
10
78D0011
WDV Series Gas Fireplace
InstallatIOn precautIOns
Consult  local  building  codes  before  beginning  the 
installation.  The  installer  must  make  sure  to  select  the 
proper  vent  system  for  installation. The  approved  5  x  8 
venting  components  are  Simpson  Duravent  and  Selkirk  
products listed on Page 41. UL1777 flexible venting is also 
approved for use on these models. Before installing vent 
kit, the installer must read this fireplace manual and vent 
kit instructions. 
Only  a  qualified  installer/service  person  should  install 
venting  system.  The  installer  must  follow  these 
safety rules:
  Wear  gloves  and  safety  glasses  for 
protection.
•  
Use extreme caution when using lad-
ders or when on rooftops.
•  
Be aware of electrical wiring locations 
in walls and ceilings.
The following actions will void the warranty on 
your venting system:
•  
Installation  of  any  damaged  venting 
component.
•  
Unauthorized modification of the vent-
ing system.
•  
Installation of any component part not 
manufactured or approved by MHSC.
•  
Installation  other  than  permitted  by  these  instruc-
tions.
VentInG InstallatIOn InFOrMatIOn
read  all  instructions  completely  and  thoroughly  before  attempting 
installation. Failure to do so could result in serious injury, property damage 
or loss of life. Operation of improperly installed and maintained venting 
system could result in serious injury, property damage or loss of life. 
W
arn
In
G
1”
FP2424
Vent pipe clearances
50”
Min. Floor 
to Center of 
Vent Pipe
Figure 7 - 
Combustible Clearances for Vent Pipe 
A minimum of 1" 
clearance to all 
sides is required 
along horizontal and 
vertical length
A minimum 1" 
clearance to 
combustibles 
permitted all 
around flue at 
outside wall
12" Vertical Rise 
Required Before 
Horizontal Run
FP2424
n
O
t
Ice
Failure to follow these instructions will 
void the warranty.
this  fireplace  must  be  vented  to  the 
outside. the venting system must neVer 
be  attached  to  a  chimney  serving  a 
separate  solid  fuel  burning  appliance. 
each gas appliance must use a separate 
vent  system.  Do  not  use  common  vent 
systems.
W
arn
In
G
W
arn
In
G
horizontal  and  vertical  sections  of  this 
vent  system  require  a  minimum  of  1" 
clearance  to  combustibles  on  all  sides, 
top and bottom.