Monessen Hearth WDV500 User Manual

Page of 48
12
78D0011
WDV Series Gas Fireplace
VentInG InstallatIOn 
Figure 8 - 
Horizontal Vent Termination Location
Vent Terminal
Air Supply Inlet
Area Where Terminals Not Permitted
Inside Corner Detail 
FOr hOrIZOntal terMInatIOn
MInIMuM DIstances 
A =  Clearance above the grade, a veranda, porch, deck, or balcony [*12" (305 mm) minimum]. 
B =  Clearance to window or door that may be opened [*12" (305 mm) minimum]. 
C =  Clearance to permanently closed window [*minimum 12" (305 mm) recommended to prevent condensation 
on window]  
 
D
 
=  Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of two (2) feet 
(610 mm) from the centerline of the terminal [18" (457 mm) minimum].  
E
 
=  Clearance to unventilated soffits [12" (305 mm) minimum]. Clearance to vinyl soffit [30" (762 mm)].
F =  Clearance to an outside corner. Figure 9  
G = Clearance to an inside corner. Figure 9  
H =  *Not to be installed above a gas meter/regulator assembly within three (3) feet (914 mm) horizontally from the 
centerline of the regulator. 
I =  Clearance to service regulator vent outlet [*3' (914 mm) minimum]. 
J =  Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance [*12" 
(305 mm) minimum]. 
K =  Clearance to a mechanical air supply inlet [*6' (1829 mm) minimum]. 
L
 
=  Clearance above a paved sidewalk or paved driveway located on public property [
**
7' (2133 mm) minimum]. 
M
 
= Clearance under veranda, porch, deck, or balcony [For Canada 12" (305 mm) minimum
***
Figure 9
As  specified  in  CSA  B149  Installation  Codes.  Note:  Local  codes  or  regulations  may  require  different 
clearances. 
**  A vent must not terminate directly above a sidewalk or paved driveway, which is located between two single-
family dwellings and serves both dwellings.   
***  Only  permitted  if  veranda,  porch,  deck,  or  balcony  is  fully  open  on  a  minimum  of  two  sides  beneath  the 
floor.
V
V
V
V
V
V
V
V
D
L
E
B
C
F
B
B
B
B
B
M
I
A
A
J
H
G
A
Operable
Fixed
Closed
Fixed
Closed
Opera-
ble
K
A
A
A
G
W
arn
In
G
always  maintain  minimum  clearances  around  vent  systems.  the  minimum 
clearances to combustibles for horizontal and vertical vent pipe are 1" at the 
top, sides and bottom of the vent system. Do not pack the open air spaces with 
insulation  or  other  materials.  this  could  cause  high  temperatures  and  may 
present a fire hazard.