Monessen Hearth WDV500 User Manual

Page of 48
16
78D0011
WDV Series Gas Fireplace
VentInG InstallatIOn 
VertIcal (thrOuGh-the-rOOF)  
applIcatIOns 
This gas fireplace has been approved for,
   Vertical installations up to 40' (12 m) in height. Up to 
a 10' (3 m) horizontal vent run can be installed within 
the vent system using a maximum of two 90° elbows. 
Figure 18
nOte: Horizontal and vertical sections of this vent system 
require a minimum 1" clearance to combustibles at the top, 
sides and bottom.
Example: 
Elbow 1   =   90°
 
Elbow 2   =   45°
 
Elbow 3   =   45°
 
Elbow 4   =   90°
Total Angular Variation  =   270°
12" Min. 
1
2
3
4
1
2
3
4
FP1179
max bends
Figure 19 - 
Maximum Elbow Usage 
FP1179
FP1966
snorkel
Figure 17 - 
Snorkel Installation, Recessed Foundation
Foundation
Recess 
Watertight Seal 
Around Pipe 
Sheet Metal 
Screws 
Wall Screws 
Snorkel 
W
arn
In
G
  Do not back fill around snorkel.
  a  clearance  of  at  least  4"  must  be 
maintained between the snorkel and 
the soil.
   Up to two 45° elbows may be used within the horizontal 
run. For each 45° elbow used on the horizontal plane, 
the maximum horizontal length must be reduced by 18" 
(450 mm). 
Example: Maximum horizontal length 
 
No elbows   =   10’ (3 m)
 
1x45° elbows   =   8.5’ (2.6 m)
 
2x45° elbows   =   7’ (2.1 m)
   A  minimum  of  an  12'  (3.6  m)  vertical  rise  is 
required.
   Two sets of 45° elbows offsets may be used within 
the vertical sections. From 0 to a maximum of 8' 
(2.5  m) of vent pipe can be used between elbows. 
Figure 19
   The  maximum  angular  variation  allowed  in  the 
system is 270°. Figure 19 
FP1183
max height
40' Maximum Height
12' Minimum Height 
10'
Maximum 
Support Straps
Every 3'
12" Min. 
FP1183
Figure 18 - 
Support Straps for Horizontal Runs