Monessen Hearth WDV500 User Manual

Page of 48
14
78D0011
WDV Series Gas Fireplace
VentInG InstallatIOn 
VertIcal/hOrIZOntal terMInatIOn  
cOnFIGuratIOns
since it is very important that the venting system main-
tain its balance between the combustion air intake and 
the flue gas exhaust, certain limitations as to vent con-
figurations apply and must be strictly adhered to.
The Vent Graph, showing the relationship between vertical 
and horizontal side wall venting, will help to determine the 
various dimensions allowable. Figure 10 
nOte: Horizontal and vertical sections of this vent system 
require a minimum of 1" clearance to combustibles at the 
top, sides and bottom. 
When vent exits through foundations less than 20" below 
outcrop, the termination must be flush up with outcropped 
wall above.
It is best to locate the fireplace in such a way that minimizes 
the number of offsets and horizontal vent length.
The horizontal vent run refers to the total length of vent 
pipe from the flue collar of the fireplace (or the top of the 
Transition Elbow) to the face of the finished outside wall. 
   The  maximum  number  of  90°  elbows  per  side  wall 
installation is three (3). Figure 11 
   A minimum of 12" is required before a 90° elbow. If a 90° 
elbow is fitted directly after 12" vertical section mounted 
to the top of the fireplace, the maximum horizontal vent 
run before the termination or a vertical rise is 36” (914 
mm). Figure 12
FP1176
max 90 bends
Figure 11 - 
Maximum Three (3) 90° Elbows Per Installation
3 x 90°
Elbows
12" Min.
FP1176
In  Figures  13  and  14  dimension A  plus  B  must  not  be 
greater than 17' (5.2 m).
   The maximum number of 45° elbows permitted per side 
wall installation is two (2). These elbows can be installed 
in either the vertical or horizontal run. 
   For each 45° elbow installed in the horizontal run, the 
length of the horizontal run MUST be reduced by 18" (45 
cm). This does not apply if the 45° elbows are installed 
on the vertical part of the vent system.
   The maximum number of elbow degrees in a system is 
270°. Figure 15
Figure 12 - 
Maximum Horizontal Run with No Rise
Max 20"
Max 20"
36" 
(914 mm) 
Max.
36" 
(914 mm) 
Max.
FP1177
max horizontal run
12”
(610 mm)
FP1177
   If a 90° elbow is used in the horizontal vent run (level 
height maintained) the horizontal vent length is reduced 
by 36". Refer to Page 17, Figures 11 and 12. This does 
not apply if the 90° elbows are used to increase or redi-
rect a vertical rise. Figure 14
Example: According to the vent graph (Page 13) the maxi-
mum horizontal vent length in a system with a 10' vertical 
rise is 17
Z\x’ (5.3 m) and if a 90° elbow is required in the 
horizontal vent it must be reduced to 14
Z\x' (4.4 m). 
Figure 13 - 
Horizontal Run Reduction 
A
B
10’
90°
FP2427
Horizontal run 
reduction
FP2427