Monessen Hearth 624WBPF User Manual
7
53D9052
624WBPF Woodburning Fireplace
clearaNceS
FP2345
MPL features
MPL features
Figure 3
Residential Installation
Residential Installation
Chimney Cap
Roof Flashing
(Flue Outlet Height)
Storm Collar
14 ft. = Min. Height (No offsets)
14 ft. = Min. Height (2 30° Elbows)
21 ft. = Min. Height (4 30° Elbows)
86 ft. = Max. Height (Chimney support
every 35 ft.)
14 ft. = Min. Height (2 30° Elbows)
21 ft. = Min. Height (4 30° Elbows)
86 ft. = Max. Height (Chimney support
every 35 ft.)
11CF1 (1 ft. pipe)
11CF18 (1Z\x ft. pipe)
11CF3 (3 ft. pipe)
11CF4 (4 ft. pipe)
Maintain 2” Minimum Air
Space Between Chimney
and Combustibles
11CF18 (1Z\x ft. pipe)
11CF3 (3 ft. pipe)
11CF4 (4 ft. pipe)
Maintain 2” Minimum Air
Space Between Chimney
and Combustibles
Gas Line
(Optional)
(Optional)
Flexible Duct
Type FP-4-U
Type FP-4-U
Combustion Air
Assembly (Optional)
Assembly (Optional)
Metal Safety Strip
(Floor Line)
Firestop
(Requires 17 x 17 framing)
(Requires 17 x 17 framing)
Nail to Framing Mem-
bers Each Side
bers Each Side
Firestop
1/2” Min. Air Space to
Combustibles
Combustibles
FP2345
Combustible materials should not be installed below
top spacer. Noncombustible materials such as brick
or tile may be used to trim face or the fireplace, com-
bustibles must not overlap the black painted face of
fireplace more than 1/8”.
top spacer. Noncombustible materials such as brick
or tile may be used to trim face or the fireplace, com-
bustibles must not overlap the black painted face of
fireplace more than 1/8”.
N
ote