Monessen Hearth 624WBPF User Manual

Page of 32
9
53D9052
624WBPF Woodburning Fireplace
Floor ProtectioN
If this fireplace is installed on a combustible floor, the floor area 16 inches in front of, and 8 inches ei-
ther side of the fireplace opening must be protected by an insulating noncombustible hearth extension. 
Figures 6 & 7
With either type hearth extension minor shifting of the supporting floor or expansion and contraction 
may eventually cause a crack to develop between the hearth extension and the face of the fireplace. 
To help prevent the crack from developing, the hearth extension materials must be firmly fastened in 
place. Wall ties should be screwed to the face of the fireplace and imbedded in the mortar joints of 
brick, stone, or other non-combustible materials. The metal safety strip packed with the fireplace must 
be placed beneath the fireplace and extended under the hearth extension or into a mortar joint of the 
hearth extension as shown by Figure 8. In the event a crack does eventually develop, the metal safety 
strip will serve as a barrier to prevent sparks or embers from falling from the fireplace onto combustible 
flooring materials.
Note: If noncombustible hearth extension materials are to be 
placed at or below the level of the bottom of the fireplace, insu-
lation board is not required.
If the fireplace is recessed into the floor or the hearth is elevat-
ed with combustible materials, an MHSC H1652 hearth exten-
sion kit or equivalent must be used for additional protection.
FP2349
fireplace location
16” 
36” Min.
8”
Hearth 
Extension
Wall Shield 
Installed Flush 
with Wall 
Board
(16” x 36” x 
1/2” thick Non-
combustible 
Board with ‘R’ 
Factor of 43 or 
Less)
Hearth 
Extension
Wall Shield on top of 
Wall Board
(Model WS or Equiva-
lent)
Glass
Glass Door
Glass Door
1/2” Air Space
FP2349
Figure 6
FP2350
floor protection
8”
29”
Min.
4”
Min.
Hearth 
Extension
Glass Door
Glass Door
Glass
Hearth 
Extension
Installation Minimums 
with No Wall Shields
Finished Combustible 
Wall Clearance from 
Fireplace Screen Open-
ing
FP2350
Figure 7
FP2183
safety strip
1/09
2”
2”
2”
Metal Safety 
Strip
(2 Required)
Special ‘Z’ 
Metal Safety 
Strip
(2 Required)
FP2183
Figure 8