CL36D AND CR36D INSTALLATION INSTRUCTIONS
WARNING!
Never install a single wall slip section or smoke-pipe in a chase structure. The higher temperature of this single
wall pipe may radiate sufficient heat to combustible chase materials to cause a fire.
WARNING!
Detailed instructions for installation of the chase top, storm collar and termination cap are packaged with these
parts. To avoid danger of fire, all instructions must be strictly followed, including the provision of air space clearance
between chimney system and enclosure. To protect against the effects of corrosion on those parts exposed to the
weather, we recommend that the chase top and termination cap be painted with a rust-resistant paint.
Figure 24 - Installing an ST375 Square
Termination Cap
c. For  installations  utilizing  an  ST375  square
termination  cap  the  last  chimney  section  must
not be more than 4½” below the chase top. See
Figure 24.
d. For installation utilizing a TS345/TS345P Square
Termination Cap, the uppermost chimney section
must not be more than 3” below the chase top.
See Figure 25.
e. Attach  the  chase  top  (CT35)  to  the  top  of  the
chase.
f.
Install  the  termination  cap,  following  the
instructions provided with it.
Figure 25 - Installing a TS345/TS345P
Square Termination Cap