5100-I  WOOD INSERT
R
250-1960  Rev B
FACTORY BUILT ZERO CLEARANCE FIREPLACE 
(USA INSTALLATONS ONLY)
The Quadra-Fire 5100-I  Insert is listed to UL Standards for Safety 127 and approved for installation and use in factory built 
zero clearance fireplaces conforming to the following specifications:
The following modifications of factory built fireplaces are permissible:  1) removal of damper;  2) removal of smoke shelf 
or baffle;  3) removal of ember catches;  4) removal of fire grate;  5) removal of viewing screen/curtain; and,  6) removal of 
doors.   
NOTE:  Installation into fireplaces without a permit will void the listing.
The factory built chimney must be listed per UL 127 and meet the type HT requirements of UL 103.  Factory built fireplace 
chimneys tested to UL 127-1998, may be at the fireplace manufacturer’s option, tested to the same criteria as UL 103 HT 
requirements.  If the chimney is not listed as meeting HT requirements, or if the factory built fireplace was tested prior to 
1998, a full height listed chimney liner must be installed from the appliance flue collar to the chimney top.  The liner must 
meet type HT requirements (2100ºF) per UL 1777.  The liner must be securely attached to the insert flue collar and the 
chimney top.  To prevent room air passage to the chimney cavity of the fireplace, seal either the damper area around the 
chimney liner with high temperature sealant or the fireplace front with fiberglass batting.
The fireplace must not be altered, except that the damper may be removed to accommodate a direct-connect starter pipe 
or chimney liner, and external trim pieces which do not affect the operation of the fireplace may be removed providing 
they can be stored on or within the fireplace for reassembly if the insert is removed.  The permanent metal warning label 
provided must be attached to the back of the fireplace, with screws or nails, stating that the fireplace may have been 
altered to accommodate the insert, and must be returned to 
original condition for use as a conventional fireplace.  
If the hearth extension is lower than the fireplace opening, 
the portion of the insert extending onto the hearth must be 
supported.  Manufacturer designed adjustable support kit 
can be ordered from your dealer.  (See page 16).
Final approval of this installation type is contingent upon 
the authority having jurisdiction.
Listed Liner 
Mantel 
SEAL DAMPER AREA OR FACE SEAL
Figure 11A - Installation Into A Factory Built 
  Zero Clearance Fireplace
36”
24”
19”
915mm
610mm
483mm
Minimum Width of cavity opening:
Minimum Height:
Minimum Depth from front to rear: