TABLE 8:  COOLING CAPACITY DM120 (10 TON) UNIT
Air On
Evap. Coil
Temperature of Air on Condenser Coil 85°F
Temperature of Air on Condenser Coil 95°F
CFM
WB
(°F)
Tot.
Cap.*
(MBH)
Tot.
Input
(kW)
Sensible Capacity (MBH)
*
Return Dry Bulb (°F)
Tot.
Cap.
*
(MBH)
Tot.
Input
(kW)
Sensible Capacity (MBH)
*
Return Dry Bulb (°F)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
3000
72 132
11.0
76
68
59
50
42
-
-
125
11.7
74
65
57
48
40
-
-
67 124
10.7
96
87
79
70
62
53
45
116
11.4
93
84
75
67
58
50
41
62 116
10.5
115
106
98
89
81
72
64
106
11.1
106
100
91
82
74
65
57
57 110
10.3
110
109
101
92
83
75
66
106
11.1
106
103
95
86
78
69
61
3500
72 135
11.1
83
73
63
53
43
-
-
129
11.8
82
72
62
52
41
-
-
67 127
10.8
104
94
84
74
64
54
44
120
11.5
102
92
82
72
62
52
42
62 119
10.6
118
114
105
95
84
74
64
110
11.2
110
106
99
89
79
69
58
57 112
10.4
112
112
108
98
87
77
67
109
11.2
109
108
103
93
83
73
63
4000
72 138
11.2
91
79
67
56
44
-
-
133
12.0
90
78
67
55
43
-
-
67 130
10.9
113
101
90
78
66
55
43
124
11.7
112
100
89
77
65
54
42
62 121
10.7
121
121
111
100
88
76
65
113
11.3
113
113
107
95
84
72
60
57 115
10.5
115
115
115
103
91
80
68
113
11.3
113
113
111
100
88
76
65
4500
72 141
11.3
98
85
71
58
45
-
-
135
12.0
96
83
70
56
43
-
-
67 132
11.0
122
108
95
82
69
55
42
126
11.7
119
106
92
79
66
53
39
62 124
10.7
124
124
118
105
92
78
65
115
11.4
115
115
112
98
85
72
58
57 117
10.5
117
117
117
104
90
77
64
115
11.4
115
115
114
101
88
74
61
5000
72 144
11.3
105
90
75
60
45
-
-
138
12.1
102
87
72
58
43
-
-
67 135
11.0
130
116
101
86
71
56
41
128
11.8
126
111
96
81
67
52
37
62 126
10.8
126
126
125
110
95
80
65
117
11.5
117
117
116
101
86
71
57
57 119
10.6
119
119
119
105
90
75
60
117
11.5
117
117
117
102
87
72
57
Temperature of Air on Condenser Coil 105°F
Temperature of Air on Condenser Coil 115°F
3000
72 117
12.4
70
62
53
45
36
-
-
109
13.1
67
58
50
41
33
-
-
67 
107
12.0
89
80
71
63
54
46
37
97
12.5
85
76
67
59
50
42
33
62 97
11.6
97
94
85
77
68
60
51
88
12.2
88
88
80
71
62
54
45
57 98
11.7
98
96
88
79
71
62
54
91
12.3
91
89
81
72
64
55
46
3500
72 121
12.5
78
68
58
48
38
-
-
113
13.2
75
64
54
44
34
-
-
67 110
12.1
98
88
78
68
57
47
37
100
12.6
94
83
73
63
53
43
33
62 100
11.7
100
99
93
83
73
62
52
91
12.3
91
91
87
76
66
56
46
57 
102
11.8
102
100
95
85
75
65
55
94
12.4
94
93
88
78
67
57
47
4000
72 124
12.7
86
74
63
51
39
-
-
116
13.4
82
70
59
47
35
-
-
67 113
12.2
107
96
84
72
61
49
37
103
12.8
103
91
79
68
56
44
33
62 103
11.9
103
103
100
89
77
65
54
94
12.4
94
94
94
82
70
59
47
57 105
11.9
105
105
103
91
80
68
56
97
12.5
97
97
95
83
71
60
48
4500
72 127
12.8
93
79
66
53
39
-
-
119
13.5
89
76
63
49
36
-
-
67 
116
12.3
112
102
88
75
62
49
35
106
12.9
106
98
84
71
58
45
31
62 106
12.0
106
106
104
91
77
64
51
96
12.5
96
96
96
83
70
56
43
57 107
12.0
107
107
106
93
80
66
53
99
12.6
99
99
98
85
72
59
45
5000
72 130
12.9
99
84
69
54
40
-
-
123
13.6
96
81
66
51
37
-
-
67 119
12.4
117
108
93
78
63
48
33
109
13.0
109
104
90
75
60
45
30
62 108
12.1
108
108
107
93
78
63
48
99
12.7
99
99
99
84
69
54
39
57 110
12.1
110
110
110
95
80
65
50
102
12.7
102
102
102
87
72
57
42
Temperature of Air on Condenser Coil 125°F
3000
72 
101
13.8
64
55
46
38
29
-
-
67 87
13.0
80
72
63
55
46
38
29
62 79
12.7
79
79
74
65
57
48
40
57 83
12.9
83
82
74
65
56
48
39
3500
72 
105
14.0
71
61
51
40
30
-
-
67 90
13.2
89
79
69
59
49
39
29
62 81
12.9
81
81
80
70
60
50
40
57 86
13.0
86
85
80
70
60
50
40
4000
72 
108
14.1
78
66
55
43
31
-
-
67 92
13.3
92
86
75
63
51
40
28
62 84
13.0
84
84
84
75
64
52
40
57 88
13.1
88
88
87
75
63
52
40
4500
72 
112
14.2
86
72
59
46
32
-
-
67 96
13.4
96
94
80
67
54
41
27
62 87
13.1
87
87
87
75
62
49
35
57 91
13.2
91
91
90
77
64
51
37
5000
72 
115
14.4
93
78
63
48
33
-
-
67 99
13.6
99
99
86
71
56
41
27
62 89
13.3
89
89
89
75
60
45
30
57 94
13.4
94
94
94
79
65
50
35
*
These capacities are gross ratings.  For net 
capacity, deduct air blower motor, MBH = 3.415 
x kW.  Refer to the appropriate Blower Perfor-
mance Table for the kW of the supply air 
blower motor.
These ratings include condenser fan motors  
and the compressor motors but not the supply 
air blower motor.