York YCJD18 THRU 60 User Manual

Page of 18
561908-YTG-A-0410
2
Johnson Controls Unitary Products
All dimensions are in inches. They are subject to change with-
out notice. Certified dimensions will be provided upon request.
Physical and Electrical Data
MODEL
YCJD18S41
S3(H)
YCJD24S41
S3(H)
YCJD30S41
S3(H)
YCJD36S41
S3(H)
YCJD42S41
S3(H)
YCJD48S41
S3(H)
YCJD60S41
S3
Unit Supply Voltage
208-230V, 1
 60Hz
Normal Voltage Range 
1
187 to 252
Minimum 
Circuit 
Ampacity
9.8  12.4 14.7 17.9 21.5
21.1 34.3
Max. Overcurrent Device Amps 
2
15 20 25 30 35 35 60
Min. Overcurrent Device Amps 
3
15 15 15 20 25 25 35
Compressor Type 
Rotary
Recip
Recip
Recip
Recip
Recip
Scroll
Compressor Amps
Rated 
Load
7.4
9.3  10.6 13.1 16.0 15.7 26.2
Locked 
Rotor
40.0 43.0 54.0  74  84  84  150
Crankcase 
Heater
No No No No No No No
Fan 
Motor 
Amps
Rated 
Load
0.5 0.8 1.4 1.5 1.5 1.5 1.5
Fan 
Diameter 
Inches
17.5 
17.5 
17.5 22 22 22 24
Fan Motor
Rated 
HP
1/12 1/8 1/4 1/4 1/4 1/4 1/4
Nominal 
RPM
1100 
1075 
1100 850 850 850 850
Nominal 
CFM
1400 1950 2050 3200 2950 2950 3600
Coil
Face Area Sq. Ft.
9.60 
9.60 
9.60 
13.07 
14.16 
14.16 
18.68
Rows 
Deep
1 1 1 1 1 1 1
Fin 
Inches
23 23 23 23 23 23 23
Liquid Line Set OD (Field Installed)
3/8 
3/8 
3/8 
3/8 
3/8 
3/8 
3/8
Vapor Line Set OD (Field Installed)
5/8 
3/4 
3/4 
3/4 
7/8 
7/8 
7/8
Unit Charge (Lbs. - Oz.) 
4
3 - 3
3 - 13
3 - 14
4 - 9
4 - 5
4 - 9
5 - 6
Charge 
Per 
Foot, 
Oz.
0.58 0.62 0.62 0.62 0.67 0.67 0.67
Operating Weight Lbs.
97
129
131
145
173
173
195
Models with “H” on the end of the model number have a factory installed start kits.
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or sub-
tract the amount of refrigerant, using the difference in length multiplied by the per foot value.
B
C
A
Unit
Model
Dimensions
(Inches)
Refrigerant Connection
Service Valve Size
A
1
1. Including Fan Guard.
B
C
Liquid
Vapor
18
28
23-1/2
23-1/2
3/8”
3/4”
24
28
23-1/2
23-1/2
30
28
23-1/2
23-1/2
36
28
29
29
42
30
29
29
7/8”
48
30
29
29
60
32
33-5/8
33-5/8