York YCJD18 THRU 60 User Manual

Page of 18
561908-YTG-A-0410
Johnson Controls Unitary Products
3
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of interconnecting 
line tubing.
2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data Table.
4. For orifice or TXV matches requiring additional charge, the refrigerant needs to be weighed in for specific coil match and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator + 
adder for line set.
System Charge for Various Matched Systems
Outdoor Unit 
YCJD18S41
S3(H)
YCJD24S41
S3(H)
YCJD30S41
S3(H)
YCJD36S41
S3(H)
YCJD42S41
S3(H)
YCJD48S41
S3(H)
YCJD60S41S3
Required Orifice or TXV 
1,2
0.048/4F1
0.055/4F1
0.061/4F1
0.065/4G1
0.075/4G1
0.073/4H1
0.087/4J1
Factory Charge, lbs-oz
3 - 3
3 - 13
3 - 14
4 - 9
4 - 5
4 - 9
5 - 6
Indoor Coil
3,4
Additional Charge, oz
AHP18
0
AHP30
4
0
AHP36
2
0
AHP42
0
0
AHP/SHP60
0
0
AHX18
0
AHX30
4
0
AHX36
4
2
0
AHX42
8
2
AHX48
0
AHX60
4
AV*24
TXV  +  0
AV*36
4
2
0
AV/SV*48
TXV  +  2
0
AV/SV*60
TXV  +  2
0
F4FP024
0
F4FP036
0
F4FP040
0
F4FV060
0
0
F5FP048
8
2
4
F5FP060
0
0
F6FP018
0
F6FP030
4
0
F6FP036
4
0
F6FP042
8
2
F6FP048
TXV  +  2
0
F6FP060
4
FC/MC/PC/18
0
FC/MC/PC32
4
0
FC/MC/PC35
4
0
FC/MC/PC/36
0
FC/MC/PC37
4
2
0
FC/MC/PC43
4
2
0
0
FC/MC/PC48
8
2
4
FC/MC/PC60
0
0
FC/MC62
4
HC18
0
HC30
0
HC36
4
0
HC42
4
2
0
0
HC60
0
UC18
0
UC36
0
UC48
8
2
4
UC60
0
0
FOOTNOTES:
1. For applications requiring a TXV use 1TVM series kit.
2. Approved orifice shipped with outdoor unit.
3. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
4. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
Models 12-48 require start kits for TXV matches. Models with “H” on the end of the model number have factory installed start kits. For
models without an “H” refer to tech guide for kit number reference.