York D2HE/D2HG060 User Manual

Page of 28
036-21216-003-A-0204
Unitary Products Group
7
TABLE 5: COOLING CAPACITIES - MODELS DHE/DHG 036 - 
85°F - 95ºF
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
85°F
TOTAL 
CAP.
1
MBH
POWER
INPUT
2
SENSIBLE CAPACITY
3
ENTERING DRY BULB, °F
CFM
WB
°F
86
83
80
77
74
71
68
1500
72
55.2
3.18
35.2
30.7
26.2
 21.8
17.3
#N/A
#N/A
67
49.1
3.13
41.7
37.2
32.8
28.3
 23.8
19.4
14.9
62
44.7
3.05
44.7
43.6
39.1
34.6
 30.1
25.7
21.2
57
42.4
3.05
42.4
42.4
42.4
37.9
 33.4
29.0
24.5
1350
72
55.2
3.18
35.2
30.7
26.2
 21.8
17.3
#N/A
#N/A
67
49.1
3.13
41.7
37.2
32.8
28.3
 23.8
19.4
14.9
62
44.7
3.05
44.7
43.6
39.1
34.6
 30.1
25.7
21.2
57
42.4
3.05
42.4
42.4
42.4
37.9
 33.4
29.0
24.5
1200
72
51.9
-3.15
30.0
26.5
23.0
 19.5
16.0
#N/A
67
46.1
3.10
35.7
32.2
28.7
25.2
 21.7
18.2
14.7
62
42.0
3.02
41.2
37.7
34.2
30.7
 27.2
23.7
20.2
57
39.8
3.03
39.8
39.8
37.3
33.8
 30.3
26.8
23-3
1050
72
49.4
3.12
27.3
24.3
21.2
 182
15.2
#N/A
67
43.9
3.07
32.6
29.6
26.5
23.5
 20.5
17.4
14.4
62
40.0
2.99
37.7
34.7
31.6
28.6
 25.6
22.5
19.5
57
37.9
3.00
37.9
37.0
34.5
31.4
 28.4
25.4
22.3
900
72
46.9
3.09
24.6
22.1
19.5
16.9
14.4
 #N/A
67
41.7
3.04
29.5
26.9
24.4
21.8
 19.2
16.7
14.1
62
38.0
2.96
34.2
31.6
29.1
26.5
 23.9
21.4
18.8
57
36.0
2.97
36.0
34.2
31.7
29.1
 26.5
24.0
21.4
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
95°F
TOTAL 
CAP.
MBH
POWER
INPUT
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
CFM
WB
°F
86
83
80
77
74
71
68
1500
72
51.5
3.44
34.1
29.7
25.2
20.7
 16.2
#N/A
#N/A
67
45.8
3.35
40.2
35.7
31.3
26.8
 22.3
17.8
13.4
62
41.2
3.30
41.2
41.2
38.8
34.3
 29.8
25.3
20.9
57
39.9
3.35
39.9
39.9
39.9
35.4
31.0
26.5
22.0
1350
72
50.0
3.41
31.5
27.5
23.6
19.6
 15.6
#N/A
#N/A
67
44.5
3.32
37.2
33.2
29.2
25.3
 2 13
17.3
13.3
62
40.0
3.27
40.0
39.2
36.3
32.3
 28.3
24.3
20.3
57
38.8
3.32
38.8
38.8
37.5
33.5
 29.6
25.6
21.6
1200
72
48.6
3.38
28.9
25.4
21.9
18.4
 14.9
#N/A '
#N/A
67
43.2
3.29
34.2
30.7
27.2
23.7
 20.2
16.7
13.2
62
38.9
3.23
38.9
37.2
33.7
30.2
 26.7
23.2
19.8
57
37.6
3.29
37.6
37.6
35.1
31.6
 28.1
24.6
21.1
1050
72
46.4
3.36
26.2
23.2
20.2
17.2
 14.1
#N/A
#N/A
67
41.2
3.27
31.1
28.1
25.0
22.0
 19.0
16.0
12.9
62
37.1
3.21
36.2
34.1
31.1
28.0
 25.0
22.0
18.9
57
35.9
3.27
35.9
34.9
32.3
29.3
 26.3
23.2
20.2
900
72
44.2
3.34
23.6
21.0
18.4
15.9
 13.3
#N/A
#N/A
67
39.3
3.25
28.0
25.4
22.9
20.3
 17.7
15.2
12.6
62
35.4
3.20
33.5
30.9
28.4
25.8
 23.2
20.7
18.1
57
34.2
3.25
34.2
32.1
29.5
27.0
 24.4
21.8
19.3
1.
These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply 
this value by 3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit
2.
These ratings include the compressor and the condenser fan motors but not the supply air blower motor.  The total condenser fan motor power input 
is 0.36kW.  Refer to Tables 10 and 11  for the kW of the supply air blower motor.
3.
These capacities are gross ratings.  For net capacity, determine the kW of the supply air blower from Tables 10 and 11, multiply this value by 3.415 
MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
NOMINAL RATING
ALL SENSIBLE CAPACITY