York D2HE/D2HG060 User Manual

Page of 28
036-21216-003-A-0204
Unitary Products Group
9
TABLE 7: COOLING CAPACITIES  - MODELS DHE/DHG048
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
85°F
95°F
TOTAL 
CAP.
1
MBH
POWER
INPUT
2
SENSIBLE CAPACITY
3
TOTAL 
CAP.
1
MBH
POWER
INPUT
2
SENSIBLE CAPACITY
3
ENTERING DRY BULB, °F
ENTERING DRY BULB, °F
CFM
WB
°F
86
83
80
77
74
71
68
86
83
80
77
74
71
2000
72
59
3.3
46
40
34
28
23
-
-
55
3.5
43
37
32
26
20
-
67
53
3.2
53
49
43
38
32
26
21
49
3.4
49
47
41
35
30
24
62
47
3.2
47
47
47
42
36
30
25
44
3.4
44
44
44
38
32
26
57
47
3.1
47
47
47
41
35
29
24
43
3.3
43
43
43
37
31
26
1800
72
58
3.3
42
37
32
27
22
-
-
54
3.5
40
35
30
25
20
-
67
53
3.2
50
46
41
35
30
25
20
48
3.4
47
44
39
33
28
23
62
47
3.2
47
47
46
41
36
31
26
43
3.4
43
43
43
38
33
28
57
46
3.1
46
46
46
41
35
30
25
42
3.3
42
42
42
37
32
27
1600
72
57
3.3
39
34
30
25
21
-
-
53
3.5
37
33
28
23
19
-
67
52
3.2
47
42
38
33
29
24
19
48
3.4
45
41
36
32
27
22
62
46
3.2
46
46
45
41
36
32
27
42
3.4
42
42
43
39
34
30
57
45
3.1
45
45
45
40
36
31
27
41
3.3
41
41
41
37
32
28
1400
72
54
3.2
35
31
27
23
19
-
-
51
3.5
34
30
26
22
17
-
67
49
3.1
43
39
35
31
27
23
19
45
3.4
41
37
33
29
25
21
62
43
3.1
43
43
42
38
34
30
26
40
3.4
40
40
40
36
32
28
57
43
3.1
43
43
41
37
33
29
25
39
3.3
39
39
38
34
30
26
1200
72
51
3.2
32
29
25
22
18
-
-
48
3.5
30
27
23
20
16
-
67
46
3.1
39
35
32
28
25
21
18
42
3.5
37
34
30
27
23
20
62
41
3.1
41
41
38
35
31
28
24
38
3.4
38
38
36
33
29
26
57
40
3.0
40
40
38
34
31
27
24
37
3.4
37
37
35
31
28
24
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
105°F
115°F
TOTAL 
CAP.
1
MBH
POWER
INPUT
2
SENSIBLE CAPACITY
3
TOTAL 
CAP.
1
MBH
POWER
INPUT
2
SENSIBLE CAPACITY
3
ENTERING DRY BULB, °F
ENTERING DRY BULB, °F
CFM
WB
°F
86
83
80
77
74
71
68
86
83
80
77
74
71
2000
72
50
3.8
41
35
30
24
18
-
-
45
4.0
39
33
28
22
16
-
67
45
3.7
45
44
39
33
27
22
16
40
4.0
40
40
37
31
25
20
62
39
3.6
39
39
39
34
28
22
17
35
3.8
35
35
35
30
24
18
57
39
3.6
39
39
39
33
27
22
16
35
3.8
35
35
35
29
23
18
1800
72
50
3.8
38
33
28
23
18
-
-
45
4.0
36
31
26
21
16
-
67
44
3.7
44
41
36
31
26
21
16
40
4.0
40
39
34
29
24
19
62
39
3.6
39
39
40
35
30
25
20
35
3.9
35
35
37
32
27
22
57
38
3.6
38
38
38
33
28
23
18
34
3.8
34
34
34
29
24
19
1600
72
49
3.8
35
31
26
21
17
-
-
45
4.1
33
29
24
20
15
-
67
44
3.7
43
39
34
30
25
20
16
40
4.1
40
37
32
27
23
18
62
39
3.6
39
39
41
37
32
27
23
35
3.9
35
35
39
34
30
25
57
38
3.6
38
38
38
33
29
24
19
34
3.8
34
34
34
30
25
20
1400
72
47
3.8
32
28
24
20
16
-
-
43
4.0
30
26
22
18
14
-
67
42
3.7
39
35
31
27
23
19
15
38
4.0
37
34
29
25
21
17
62
37
3.6
37
37
38
33
29
25
21
33
3.8
33
33
35
31
27
23
57
36
3.5
36
36
35
31
27
23
18
33
3.7
33
33
31
27
23
19
1200
72
44
3.7
29
25
22
18
15
-
-
41
3.9
27
24
20
17
13
-
67
40
3.7
36
32
29
25
21
18
14
36
3.9
34
30
27
23
20
16
62
35
3.6
35
35
34
30
27
23
20
32
3.8
32
32
32
28
25
21
57
34
3.5
34
34
32
28
25
21
18
31
3.7
31
31
29
25
22
18
1.
These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance 
Table, multiply this value by 3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit
2.
These ratings include the compressor and the condenser fan motors but not the supply air blower motor.  The total condenser fan 
motor power input is 0.36kW.  Refer to Tables 10 and 11  for the kW of the supply air blower motor.
3.
These capacities are gross ratings.  For net capacity, determine the kW of the supply air blower from Tables 10 and 11, multiply 
this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
NOMINAL RATING
ALL SENSIBLE CAPACITY