TABLE 6: COOLING CAPACITIES - MODELS DHE/DHG 036 - 
105°F - 115ºF
AIR ON 
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
105°F
TOTAL 
CAP.
1
MBH
POWER
INPUT
2
SENSIBLE CAPACITY
3
ENTERING DRY BULB, °F
CFM
WB
°F
86
83
80
77
74
71
68
1500
72
47.6
3.65
32.3
27.8
23.3
 18.9
14.4
#N/A
#N/A
67
42.5
3.56
39.0
34.5
30.0
25.6
 21.1
16.6
12.1
62
38.0
3.49
38.0
38.0
36.6
32.1
 27.6
23.1
18.7
57
37.4
3.54
37.4
37.4
37.4
32.9
 28.5
24.0
19.5
1350
72
46.5
3.62
29.7
25.8
21.8
 17.8
13.8
#N/A
#N/A
67
41.6
3.53
36.0
32.0
28.0
24.0
 20.1
16.1
12.1
62
37.1
3.46
37.1
36.6
34.1
30.1
 26.1
22.2
18.2
57
36.5
3.52
36.5
36.5
35.2
31.2
 27.2
23.3
19.3
1200
72
45.4
3.60
27.2
23.7
20.2
 16.7
12.2
#N/A
#N/A
67
40.6
3.51
33.0
29.5
26.0
22.5
 19.0
15.5
12.0
62
36.2
3.44
36.2
35.2
31.7
28.2
 24.7
21.2
17.7
57
35.7
3.49
35.7
35.7
33.0
29.5
 26.0
22.5
19.0
1050
72
43.2
3.57
24.6
21.6
18.5
 12.5
#N/A
#N/A
67
38.7
3.48
29.9
26.9
23.8
20.8
 17.8
14.7
11.7
62
34.5
3.41
33.9
32.1
29.0
26.0
 23.0
19.9
16.9
57
34.0
3.47
34.0
32.9
30.3
27.2
 24.2
21.2
18.1
900
72
41.1
3.54
22.0
19.4
16.8
14.3
11.7
 #N/A
 #N/A
67
36.7
3.45
26.8
24.2
21.7
19.1
 16.5
14.0
11.4
62
32.8
3.39
31.5
28.9
26.4
23.8
 21.2
18.7
16.1
57
32.3
3.44
32.3
30.1
27.5
24.9
 22.4
19.8
17.2
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
115°F
TOTAL 
CAP.
MBH
POWER
INPUT
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
CFM
WB
°F
86
83
80
77
74
71
68
1500
72
43.6
3.85
30.4
26.0
21.5
 17.0
12.5
#N/A
#N/A
67
39.3
3.76
37.8
33.3
28.8
24.3
 19.9
15.4
10.9
62
34.8
3.67
34.8
34.8
34.4
29.9
 25.4
20.9
16.5
57
34.9
3.73
34.9
34.9
34.9
30.5
26.0
21.5
 17.0
1350
72
42.9
3.83
28.0
24.0
20.0
 16.0
12.0
#N/A
#N/A
67
38.6
3.74
34.8
30.8
26.8
22.8
 18.8
14.9
10.9
62
34.2
3.66
34.2
34.0
32.0
28.0
 24.0
20.0
16.0
57
34.3
3.72
34.3
34.3
32.9
28.9
 24.9
21.0
17.0
1200
72
42.2
3.82
25.5
22.0
18.5
 15.0
11.5
#N/A
#N/A
67
37.9
3.73
31.8
28.3
24.8
21.3
 17.8
14.3
10.8
62
33.6
3.64
33.6
33.1
29.6
26.1
 22.6
19.1
15.6
57
33.7
3.70
33.7
33.7
30.9
27.4
 23.9
20.4
16.9
1050
72
40.1
3.78
22.9
19.9
16.9
 13.8
10.8
#N/A
#N/A
67
36.1
3.69
28.7
25.7
22.6
19.6
 16.6
13.5
10.5
62
32.0
3.61
31.6
30.0
27.0
23.9
 20.9
17.9
14.9
57
32.1
3.67
32.1
30.9
28.2
25.1
 22.1
19.1
16.0
900
72
38.0
3.75
20.4
17.8
15.2
12.7
 10.1
#N/A
#N/A
67
34.2
3.66
25.6
23.0
20.4
17.9
 15.3
12.7
10.2
62
30.3
3.58
29.5
26.9
24.4
21.8
 19.2
16.7
14.1
57
30.4
3.64
30.4
28.0
25.4
22.9
 20.3
17.7
15.2
1.
These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance 
Table, multiply this value by 3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit
2.
These ratings include the compressor and the condenser fan motors but not the supply air blower motor.  The total condenser fan motor 
power input is 0.36kW.  Refer to Tables 10 and 11  for the kW of the supply air blower motor.
3.
These capacities are gross ratings.  For net capacity, determine the kW of the supply air blower from Tables 10 and 11, multiply this value 
by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
NOMINAL RATING
ALL SENSIBLE CAPACITY