Honeywell TH8110U User Manual

Page of 12
TH8110U TOUCH SCREEN PROGRAMMABLE THERMOSTATS
69-1700
8
Cycles per 
hour (cph) for 
1st Stage 
Compressor
0220
3
Compressor Stage 
1 cycles per hour 
(cph)
1-6
1-6 available; 
3 is recommended.
Cycles per 
hour (cph) for 
1st Stage 
Conventional 
Heat
0240
5
Conventional Heat 
Stage 1 cycles per 
hour (cph)
1-12
1-12 available; typical       
settings:                                                            
1—1 cph used for steam or  
gravity    system.                                                          
3—3 cph used for hot water 
systems or high efficiency 
(90% or better) fossil fuel 
forced air systems.                                                    
5—5 cph used for standard 
fossil fuel forced air 
systems.                                                  
9—9 cph used for electric 
forced air heat systems.
Not shown if 
system selection 
is heat pump. 
Selection in this 
stage changes 
default cph for 
2nd stage heat. 
Continuous 
Backlight
0280
0
Backlight not on 
continuously. 
Thermostat 
backlight comes on 
with each key 
press.
1
Backlight is on continuously 
(thermostat must have a 
common wire attached for 
this function).
Option is always 
shown; however, 
continuously on 
backlight works 
only if thermostat 
is wired with 24 
vac Common.
Additional 
Menu Choices
0290
0
Only main menu 
options are shown. 
Installer Test 
Options shown next 
(Table 7).
1,2
1—Main Menu and Regional 
Settings are shown plus 
Installer Test (Tables 5 and 7 
only).
                                                          
2—All remaining Menu/
Options shown plus Installer 
Test (Tables 5, 6 and 7).
The majority of 
application 
require only the 
Main Menu 
Options.
Table 4. Main Installer Setup Menu. (Continued)
Select
Installer 
Setup 
Number
Factory Setting
Other Choices
Comments
Option
Description
Options
Description