Siemens ST PCS 7 User Manual

Page of 344
Process I/O
ET 200M distributed I/O
AI - analog input modules
11/19
Siemens ST PCS 7 · November 2007
11
Overview
The analog input modules described here break down into 
• multi-function modules for current, voltage and temperature 
measurements, and
• special, highly accurate modules for current and voltage mea-
surements or temperature measurements. 
All modules automatically supply channel-specific and module-
internal diagnostics data, except module 6ES7 331-1KF01-
0AB0. With the latter module, channel failure is identified by the 
PCS 7 analog driver block. 
The individual channels of the analog input modules can be pa-
rameterized in groups independently of each other.
Selection and Ordering Data
Order No.
SM 331 modules for current, voltage and temperature measure-
ments
 
8 inputs, individually parame-
terizable
• Resolution 12 bit + sign
• Current measurement 0/4 to 
20 mA (8 channels; 2 wires with 
external supply or 4 wires)
• Voltage measurement 
(8 channels)
• Resistance thermometer Pt100, 
Ni100, Ni1000, LG-Ni1000 
(8 channels; 2, 3 or 4 wires) 
• Front connector required: 
40-contact
6ES7 331-1KF01-0AB0
8 inputs in 4 channel groups
Redundant design possible 
(module redundancy)
• Changeover of measurement 
type by range module per chan-
nel group
• Resolution 14 bit + sign
• Current measurement 0/4 to 
20 mA (8 channels; 2 or 4 wires)
• Voltage measurement 
(8 channels)
• Resistance thermometer Pt100, 
Ni100 (4 channels, 2 or 4 wires)
• Thermocouples type E, N, J, K, L 
(8 channels),
internal compensation or exter-
nal compensation with compen-
sating box or 0 °C cold junction
• Wire break monitoring
• Diagnostics inside module 
• Front connector required: 
20-contact
6ES7 331-7KF02-0AB0
2 inputs in 1 channel group
• Changeover of measurement 
type by range module
• Resolution 14 bit + sign
• Current measurement 0/4 to 
20 mA (2 channels; 2 or 4 wires)
• Voltage measurement 
(2 channels)
• Resistance thermometer Pt100, 
Ni100 (1 channel, 2 or 4 wires)
• Thermocouples type E, N, J, K, L 
(2 channels),
internal compensation or exter-
nal compensation with compen-
sating box or 0 °C cold junction
• Wire break monitoring
• Diagnostics inside module 
• Front connector required: 
20-contact
6ES7 331-7KB02-0AB0
B)
B) Subject to export regulations: AL: N, ECCN: EAR99H
© Siemens AG 2007