Siemens ST PCS 7 User Manual

Page of 344
Process I/O
ET 200M distributed I/O
AO - analog output modules
11/21
Siemens ST PCS 7 · November 2007
11
Overview
The analog output modules for voltage and current described 
here break down into
• modules with 12 bit resolution and various numbers of chan-
nels, and
• a high-precision module with 15 bit resolution.
The analog output modules can be parameterized in groups in-
dependently of each other and automatically supply all channel-
specific and module-internal diagnostics data.
B) Subject to export regulations: AL: N, ECCN: EAR99H
Selection and Ordering Data
Order No.
SM 332 modules for current and voltage outputs
 
2 outputs in 2 channel groups
• Resolution 12 bit + sign
• Voltage 0/1 to 5/10 V; 
±
10 V 
(2 channels; 2 or 4 wires)
• Current 0/4 to 20 mA; 
±
20 mA 
(2 channels; 2 wires)
• Parameterizable substitute val-
ue output in case of CPU stop
• Broken wire monitoring (only for 
current)
• Short circuit monitoring (only for 
voltage)
• Diagnostics inside module 
• Front connector required: 
20-contact
6ES7 332-5HB01-0AB0
4 outputs in 4 channel groups
Redundant design possible 
(module redundancy)
• Resolution 12 bit + sign
• Voltage 0/1 to 5/10 V; 
±
10 V 
(4 channels; 4 wires)
• Current 0/4 to 20 mA; 
±
20 mA 
(4 channels; 2 wires)
• Parameterizable substitute val-
ue output in case of CPU stop
• Broken wire monitoring (only for 
current)
• Short circuit monitoring (only for 
voltage)
• Diagnostics inside module 
• Front connector required: 
20-contact
6ES7 332-5HD01-0AB0
8 outputs in 8 channel groups
Redundant design possible 
(module and channel redun-
dancy)
• Resolution 12 bit + sign
• Voltage 0/1 to 5/10 V; 
±
10 V 
(8 channels; 4 wires)
• Current 0/4 to 20 mA; 
±
20 mA 
(8 channels; 2 wires)
• Parameterizable substitute val-
ue output in case of CPU stop
• Broken wire monitoring (only for 
current)
• Short circuit monitoring (only for 
voltage)
• Diagnostics inside module 
• Front connector required: 
40-contact
6ES7 332-5HF00-0AB0
4 outputs in 4 channel groups
• Resolution 15 bit + sign
• Voltage 0/1 to 5/10 V; 
±
10 V 
(4 channels; 4 wires)
• Current 0/4 to 20 mA; 
±
20 mA 
(4 channels; 2 wires)
• Parameterizable substitute val-
ue output in case of CPU stop
• Isolated by channel
• Diagnostics inside module 
• Front connector required: 
20-contact
6ES7 332-7ND02-0AB0
B)