Omron CJ1W-EIP21 User Manual
359
Connection Status Codes and Error Processing
Section 14-3
Email odva@odva.org
WEB www.odva.org
The following table shows the possible originator/target configurations.
The following table shows the likely causes of the errors causes for each con-
figuration and connection status (code).
figuration and connection status (code).
Configuration
Originator
Target
Configuration 1
CS1W-EIP21, CJ1W-EIP21,
CJ2H-CPU
CJ2H-CPU
@@
-EIP, CJ2M-
CPU3
@
CS1W-EIP21, CJ1W-EIP21,
CJ2H-CPU
CJ2H-CPU
@@
-EIP, CJ2M-
CPU3
@
Configuration 2
CS1W-EIP21, CJ1W-EIP21,
CJ2H-CPU
CJ2H-CPU
@@
-EIP, CJ2M-
CPU3
@
Other company’s device
Configuration 3
Other company’s device
CS1W-EIP21, CJ1W-EIP21,
CJ2H-CPU
CJ2H-CPU
@@
-EIP, CJ2M-
CPU3
@
Connection status
Source of error
Handling
General
Status
(hex)
Additional
Status
(hex)
Configuration 1
Configuration 2
Configuration 3
00
0000
Normal status code:
The connection has been
opened and the tag data link is
communicating normally.
opened and the tag data link is
communicating normally.
---
---
---
01
0100
Error code returned from target:
Attempted to open multiple con-
nections at the same connec-
tion.
nections at the same connec-
tion.
This error does
not occur.
not occur.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer for details on
preventing the error
from occurring in the
future.)
get’s specifications.
(Contact the target
device’s manufac-
turer for details on
preventing the error
from occurring in the
future.)
Depends on the orig-
inator’s specifica-
tions.
(Contact the origina-
tor device’s manufac-
turer for details on
preventing the error
from occurring in the
future.)
inator’s specifica-
tions.
(Contact the origina-
tor device’s manufac-
turer for details on
preventing the error
from occurring in the
future.)
01
0103
Error code returned from target:
Attempted to open a connection
with an unsupported transport
class.
with an unsupported transport
class.
This error does
not occur.
not occur.
Confirm that the tar-
get supports Class
1.
get supports Class
1.
Confirm that the
originator supports
Class 1.
originator supports
Class 1.
01
0106
Duplicate consumers:
Attempted to open multiple con-
nections for single-consumer
data.
nections for single-consumer
data.
If the tag data link
is stopped or
started, this error
may occur accord-
ing to the timing,
but the system will
recover automati-
cally.
is stopped or
started, this error
may occur accord-
ing to the timing,
but the system will
recover automati-
cally.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
get’s specifications.
(Contact the target
device’s manufac-
turer.)
If the tag data link is
stopped or started,
this error may occur
according to the tim-
ing, but the system
will recover automat-
ically.
stopped or started,
this error may occur
according to the tim-
ing, but the system
will recover automat-
ically.
01
0107
Error code returned from target:
Attempted to close a connec-
tion, but that connection was
already closed.
tion, but that connection was
already closed.
This error does
not occur.
not occur.
This error does not
occur.
occur.
This is not an error
because the connec-
tion is already
closed.
because the connec-
tion is already
closed.
01
0108
Error code returned from target:
Attempted to open a connection
with an unsupported connection
type.
with an unsupported connection
type.
This error does
not occur.
not occur.
Check which con-
nection types can be
used by the target.
(Contact the manu-
facturer.)
nection types can be
used by the target.
(Contact the manu-
facturer.)
Only multicast and
point-to-point can be
set.
point-to-point can be
set.
Check which con-
nection types can be
used by the origina-
tor.
nection types can be
used by the origina-
tor.
(An error will occur if
a connection other
than multicast or
point-to-point is set.)
a connection other
than multicast or
point-to-point is set.)