Omron CJ1W-EIP21 User Manual

Page of 464
359
Connection Status Codes and Error Processing
Section 14-3
Email odva@odva.org
WEB www.odva.org 
The following table shows the possible originator/target configurations.
The following table shows the likely causes of the errors causes for each con-
figuration and connection status (code).
Configuration
Originator
Target
Configuration 1
CS1W-EIP21, CJ1W-EIP21, 
CJ2H-CPU
@@
-EIP, CJ2M-
CPU3
@
 
CS1W-EIP21, CJ1W-EIP21, 
CJ2H-CPU
@@
-EIP, CJ2M-
CPU3
@
 
Configuration 2
CS1W-EIP21, CJ1W-EIP21, 
CJ2H-CPU
@@
-EIP, CJ2M-
CPU3
@
 
Other company’s device
Configuration 3
Other company’s device
CS1W-EIP21, CJ1W-EIP21, 
CJ2H-CPU
@@
-EIP, CJ2M-
CPU3
@
 
Connection status
Source of error
Handling
General 
Status 
(hex)
Additional 
Status 
(hex)
Configuration 1
Configuration 2
Configuration 3
00
0000
Normal status code:
The connection has been 
opened and the tag data link is 
communicating normally.
---
---
---
01
0100
Error code returned from target:
Attempted to open multiple con-
nections at the same connec-
tion.
This error does 
not occur.
Depends on the tar-
get’s specifications.
(Contact the target 
device’s manufac-
turer for details on 
preventing the error 
from occurring in the 
future.)
Depends on the orig-
inator’s specifica-
tions.
(Contact the origina-
tor device’s manufac-
turer for details on 
preventing the error 
from occurring in the 
future.)
01
0103
Error code returned from target:
Attempted to open a connection 
with an unsupported transport 
class.
This error does 
not occur.
Confirm that the tar-
get supports Class 
1.
Confirm that the 
originator supports 
Class 1.
01
0106
Duplicate consumers:
Attempted to open multiple con-
nections for single-consumer 
data.
If the tag data link 
is stopped or 
started, this error 
may occur accord-
ing to the timing, 
but the system will 
recover automati-
cally.
Depends on the tar-
get’s specifications.
(Contact the target 
device’s manufac-
turer.)
If the tag data link is 
stopped or started, 
this error may occur 
according to the tim-
ing, but the system 
will recover automat-
ically.
01
0107
Error code returned from target:
Attempted to close a connec-
tion, but that connection was 
already closed.
This error does 
not occur.
This error does not 
occur.
This is not an error 
because the connec-
tion is already 
closed.
01
0108
Error code returned from target:
Attempted to open a connection 
with an unsupported connection 
type.
This error does 
not occur.
Check which con-
nection types can be 
used by the target. 
(Contact the manu-
facturer.)
Only multicast and 
point-to-point can be 
set.
Check which con-
nection types can be 
used by the origina-
tor.
(An error will occur if 
a connection other 
than multicast or 
point-to-point is set.)