Omron CJ1W-EIP21 User Manual

Page of 464
360
Connection Status Codes and Error Processing
Section 14-3
01
0109
Error code returned from target:
The connection size settings 
are different in the originator 
and target.
Check the connection sizes set in the originator and target.
01
0110
Error code returned from target:
The target was unable to open 
the connection, because of its 
operating status, such as down-
loading settings.
Check whether 
the tag data link is 
stopped at the tar-
get. (Restart the 
tag data link com-
munications with 
the control bit.)
Depends on the tar-
get’s specifications.
(Contact the target 
device’s manufac-
turer.)
Check whether the 
tag data link is 
stopped at the origi-
nator. (Restart the 
tag data link commu-
nications with the 
control bit.)
01
0111
Error code returned from target:
The RPI was set to a value that 
exceeds the specifications.
This error does 
not occur.
Check the target’s 
RPI setting specifica-
tions.
Set the originator’s 
RPI setting to 10 
seconds or less.
01
0113
Error code generated by origi-
nator or returned from target:
Attempted to open more con-
nections than allowed by the 
specifications (CJ2M: 32, other 
CPU Units: 256).
Check the con-
nection settings 
(number of con-
nections) at the 
originator and tar-
get.
Check the connec-
tion settings (number 
of connections) at 
the originator and 
target.
Check the connec-
tion specifications for 
another company’s 
devices.
Check the connec-
tion settings (number 
of connections) at 
the originator and 
target.
Check the connec-
tion specifications for 
another company’s 
devices.
01
0114
Error code returned from target:
The Vendor ID and Product 
Code did not match when open-
ing connection.
This error does 
not occur.
Depends on the tar-
get’s specifications.
(Contact the target 
device’s manufac-
turer.)
Confirm that the tar-
get device’s EDS file 
is correct.
Check the origina-
tor’s connection set-
tings.
01
0115
Error code returned from target:
The Product Type did not match 
when opening connection.
This error does 
not occur.
Depends on the tar-
get’s specifications.
(Contact the target 
device’s manufac-
turer.)
Confirm that the tar-
get device’s EDS file 
is correct.
Check the origina-
tor’s connection set-
tings.
01
0116
Error code returned from target:
The Major/Minor Revisions did 
not match when opening con-
nection.
Check the major 
and minor revi-
sions set for the 
target device and 
connection. If nec-
essary, obtain the 
EDS file and set it 
again.
Depends on the tar-
get’s specifications.
(Contact the target 
device’s manufac-
turer.)
Confirm that the tar-
get device’s EDS file 
is correct.
Check the origina-
tor’s connection set-
tings.
01
0117
Error code returned from target:
The tag set specified in the con-
nection’s target variables does 
not exist.
Check whether 
the originator and 
target tag sets 
and tags are set 
correctly.
CJ2 CPU Units 
Only: Check sym-
bol settings in the 
CPU Unit.
Depends on the tar-
get’s specifications.
(Contact the target 
device’s manufac-
turer.)
Check the origina-
tor’s connection set-
tings. Check whether 
the target’s tag sets 
and tags are set cor-
rectly.
CJ2 CPU Units Only: 
Check symbol set-
tings in the CPU 
Unit.
Connection status
Source of error
Handling
General 
Status 
(hex)
Additional 
Status 
(hex)
Configuration 1
Configuration 2
Configuration 3