Siemens 440 User Manual

Page of 78
Issue 10/06   
6  Commissioning 
MICROMASTER 440   
Operating Instructions (Compact) 
39
 
6.4.7 
Analog output (DAC) 
 
CI: DAC 
Defines function of the 0 - 20 mA analog output. 
21  CO: Output frequency (scaled according to P2000) 
24  CO: Frequency inverter output frequency (scaled according to P2000) 
25  CO: Output voltage (scaled according to P2001) 
26  CO: DC link voltage (scaled according to P2001) 
27  CO: Output current (scaled according to P2002)  
NOTE 
For P0771 to P0781, the following applies: 
Index 0  :  Analog output 1 (DAC1), terminals 12, 13 
Index 1  :  Analog output 2 (DAC2), terminals 26, 27 
 
P0773 =...    Smooth time DAC 
Defines smoothing time [ms] for analog output signal. This parameter enables smoothing 
for DAC using a PT1 filter. 
 
Permit absolute value 
Decides if the absolute value of the analog output is used. If enabled, this parameter will 
take the absolute value of the value to be outputed. If the value was originally negative then 
the corresponding bit in r0785 is set, otherwise it is cleared. 
 0  OFF 
 1  ON 
 
DAC type 
Defines the analog output type.  
 0  Current output 
 1  Voltage output 
NOTE 
•  P0776 changes the scaling of r0774 (0 – 20 mA ⇔ 0 – 10 V) 
•  Scaling parameters P0778, P0780 and the dead zone are always entered in 0 – 20 mA 
For the DAC as voltage output, the DAC outputs must be terminated using a 500 
Ω resistor
 
Value x1 of DAC scaling 
Defines the output characteristic value 
x1 as a %.  
This parameter represents the lowest 
analog value as a % of P200x  
(depending on the setting of P0771). 
 
Value y1 of DAC scaling 
This parameter represents the value for 
x1 in mA. 
 
Value x2 of DAC scaling 
Defines the output characteristic value 
x2 as a %.  
This parameter represents the lowest 
analog value as a % of P200x  
(depending on the setting of P0771). 
20
P0780
y
2
P0778
y
1
P0777
x
1
P0779
x
2
100 %
mA
P0781
%
 
Value y2 of DAC scaling 
This parameter represents the value for x2 in mA. 
 
Width of DAC deadband 
Sets width of deadband in [mA] for analog output. 
21
P0771 = ... 
P0776 = ... 
0
 
0.0 %
 
0
100.0 %
P0777 = ... 
P0778 = ... 
P0779 = ... 
20
 
P0780 = ... 
0
 
P0781 = ... 
2 ms
 
P0775 = ...