6  Commissioning 
Issue 10/06 
 
MICROMASTER 440 
40 
Operating Instructions (Compact) 
 
 
6.4.8 
Motor potentiometer (MOP) 
 
P1031 =... 
 
Setpoint memory of the MOP 
Saves last motor potentiometer setpoint (MOP) that was active before OFF command or 
power down. 
  0  MOP setpoint will not be stored 
  1  MOP setpoint will be stored (P1040 is updated) 
 
P1032 =... 
 
Inhibit negative MOP setpoints 
 
0  Neg. MOP setpoint is allowed 
  1  Neg. MOP setpoint inhibited 
 
P1040 =...    Setpoint of the MOP 
Determines setpoint for motor potentiometer control. 
 
MOP ramp-up and ramp-down times are defined by the parameters P1120 and P1121. 
 
Selection
DIN
BOP
UP button
USS control word
r2032 Bit13
USS control word
r2032 Bit14
or
P0702 = 13
(DIN2)
P0703 = 14
(DIN3)
P0719 = 0, P0700 = 1, P1000 = 1
MOP up
MOP down
P0719 = 1, P0700 = 2
or
P0719 = 0, P0700 = 2, P1000 = 1
P0719 = 11
or
P0719 = 0, P0700 = 4, P1000 = 1
P0719 = 41
DOWN button
Possible parameter settings for the selection of MOP:
USS on
BOP link
USS control word
r2036 Bit13
USS control word
r2036 Bit14
or
P0719 = 0, P0700 = 5, P1000 = 1
P0719 = 51
USS on
COM link
CB control word
r2090 Bit13
r2090 Bit14
or
P0719 = 0, P0700 = 6, P1000 = 1
P0719 = 61
CB
CB control word
 
 
0
 
1
 
5.00 Hz