6.4.18 Converter-specific 
Functions 
6.4.18.1 Flying 
start 
 
Flying start
 
 
Starts inverter onto a spinning motor by rapidly changing the output frequency of the 
inverter until the actual motor speed has been found. 
  0  Flying start disabled 
  1  Flying start is always active, start in direction of setpoint 
  2  Flying start is active if power on, fault, OFF2, start in direction of setpoint 
  3  Flying start is active if fault, OFF2, start in direction of setpoint 
  4  Flying start is always active, only in direction of setpoint 
  5  Flying start is active if power on, fault, OFF2, only in direction of setpoint 
  6  Flying start is active if fault, OFF2, only in direction of setpoint 
 
Motor-current: Flying start
 (entered in %) 
Defines search current used for flying start. 
 
Search rate: Flying start
 (entered in %) 
Sets factor by which the output frequency changes during flying start to synchronize with 
turning motor. 
6.4.18.2 Automatic 
restart 
 
Automatic restart
 
 
Configures automatic restart function. 
 0  Disabled 
  1  Trip reset after power on 
  2  Restart after mains blackout 
  3  Restart after mains brownout or fault 
  4  Restart after mains brownout 
  5  Restart after mains blackout and fault 
  6  Restart after mains brown/blackout or fault 
 
P1210 = ... 
1
 
0
 
100 %
 
100 %
 
P1200 = ... 
P1202 = ... 
P1203 = ?